Ventilation: the inlet grids and ventilation fan should be installed in such a way that any
recirculation of cooling air to the compressor or dryer is avoided.
The air velocity to the grids must be limited to 5 m/s (200 in/s).
The required ventilation capacity to limit the temperature of the compressor room can be
calculated from the following formula:
Q
= 0.92 N / ΔT
v
Q
= Required ventilation capacity in m
v
N = Shaft input of compressor in kW
ΔT = Temperature increase in the compressor room in °C
4.2

Dimension drawings

The dimension drawing can be found in the technical documentation supplied with the unit.
Dimension drawing
9828 0832 60
9828 0832 61
9828 0832 62
Text on drawings
Emergency stop switch
Power supply
Cooling air and compressor inlet
Cooling air outlet of compressor and motor
Service panel
Compressor controller
Oil level indicator
Compressed air outlet (G1/2" Female)
Forklift openings
Valve rotation
Center of gravity
Cubicle door fully open
Anchorpoints in base
Air receiver safety valve
Vessel anchor points
Air receiver manual drain (G3/8" Female)
Dryer dewpoint indicator
Condensate drain integrated dryer
Dryer inlet cooling air
Dryer outlet cooling air
2920 7113 41
3
/s
Model
Floor-mounted
Tank-mounted
Tank-mounted with dryer
Translation or explanation
Emergency stop switch
Power supply
Cooling air and compressor inlet
Cooling air outlet of compressor and motor
Service panel
Compressor controller
Oil level indicator
Compressed air outlet
Forklift openings
Valve rotation
Center of gravity
Cubicle door fully open
Anchorpoints in base
Air receiver safety valve
Vessel anchor points
Air receiver manual drain
Dryer dewpoint indicator
Condensate drain integrated dryer
Dryer inlet cooling air
Dryer outlet cooling air
47