Pro‐OX 2510 Iron Filter Installa on & Startup Guide
although you do not want to see a large amount of media coming out, which would mean you have very
high water pressure, or the drain flow for the Fleck 2510 is missing.
21. If possible verify that the backwash flow is 10 gallons per minute, which is the recommended backwash
flow rate for 1.0 and 1.5 cubic foot models. If you have a 2.5 cubic foot Pro-OX it should be backwash-
ing at 15 gallons per minute. You can easily run the drain hose to a bucket and using a watch verify the
flow rate in gallons per minute. An adequate backwash is cri cal to properly clean the Pro-OX media
and prevent it from cemen ng together.
22.
Refer to your Fleck 2510 service manual for more informa on about how your control valve is pro-
grammed if desired.
Maintaining Your 2510 Pro‐OX Iron Filter System:
There is li le or no maintenance required. Every 6 – 10 years the Pro-OX media can be replaced for best
results.
Troubleshoo ng Your 2510 Pro‐OX Iron Filter System:
Measure the backwash flow rate by pu ng the system into a backwash mode and pu ng the drain tube
into a 5 gallon bucket and ming the flow rate. A 0.75 cubic foot system should flow at 5 gallons in one mi-
nute, so the 5 gallon bucket should fill in one minute. The 1.0 cubic foot system should flow at 7 GPM dur-
ing backwash.

Program Se ngs

Check to make sure the control valve has been set correctly. In some cases a nightly backwash is required
for best results. Adjust backwash frequency to every 1 to 2 nights if necessary.

What to Do If Your Filter Tank Does Not Sit Level on the Floor

Your black filter tank base is not glued to the bo om of your tank. Occasionally tank bases will become
crooked during shipment. If you find that that your tank does not sit level on the floor, you can easily adjust
it by holding the empty tank and rapping it on a concrete or solid floor once or twice in order to level it.
WARNING: Don't Over‐Tighten 2510 Control When Installing on Tank