Connect AC Power to NCS 1001

Connect AC Power to NCS 1001
Caution
The voltage rating value for AC power ranges either between 200 V to 240 V or between 100 V to 127 V
depending on the standards in various countries.
Note
Figure 34: Hot Area on PSU Faceplate
Procedure
Step 1
Verify that the AC cable is installed in the correct AC source panel. Ensure that either the fuse is removed or
the circuit breaker is in the off position and locked out.
Note
Step 2
Attach the AC power cable to the cable connector in the AC power module.
Step 3
Close the cable clamp to secure the power cable.
Hardware Installation Guide for Cisco NCS 1001
36
NCS 1001 relies on the protective devices in the building installation to protect against short circuit, overcurrent,
and ground faults. Ensure that the protective devices comply with local and national electrical codes.
A dual pole breaker is needed for the installation. The rating of the dual pole breaker is 16A for International
and 20A for USA and Canada.
For an AC power supply, fuse or breaker rating must not exceed 20A.