7500-Rev2.5 Greensand Filter Installation & Startup Guide
Set Regen Time
This is the time your system will backwash. Default is 2:00 AM
Set Backwash Time Length
Set B. S. R. Time
"Brine Slow Rinse" time. Set for 60 minutes. This is where the potassium
permanganate solution is drawn in to the system.
Set Secondary Backwash Time
Set Fast Rinse Time
Set B. R. Time
"Brine Refill" – this is where the pot perm tank refills.
Pick your iron filter size and enter minutes.
Maximum Days for Regen.
between each backwash. The recommended initial setting for the
Greensand Filter is every 4 days for families or heavy use and every 7 days
for 1 to 2 persons in the home.
If you experience pressure loss or see iron in water in between backwashes, increase frequency of
backwash up to once per day.
Usage Logs:
The following are diagnostic menus you can review later if you wish:
Daily Usage Log
Daily Peak Usage
Weekly Usage Log
Weekly Peak Usage
Monthly Usage Log
Monthly Peak Usage
Review Regen. Times
11
Set for 10 minutes. This is the first cycle.
Set for 8 minutes.
Set for 8 minutes.
Set to 4 Days. This refers to the days
www.cleanwaterstore.com
B.R. Times
0.75 CF
4 MIN.
1.0 CF
5 MIN.
1.5 CF
6 MIN.
2.0 CF
7 MIN.
2.5 CF
8 MIN.
rev012122