◆ 12.2 User Settings
The user can make the following settings with the front panel controls:
(1) PC Interface Selection (Stand-Alone or W/S Mode)
(2) Communications Baud Rate Selection (9600, 4800 or 2400 bps)
(3) Power Outage Beeper Setting (Beep/Silent)
(4) Frequency Sync Range Setting (1, 3 or 5%)
(5) Autostart after power recovery: Restart or Standby (Stop Output)
(6) Response time of INV ON/STAND BY button
(7) Ring Signal Start Setting (Enable/Disable)
(8) Battery Starting Frequency (50/60 Hz)
All settings are performed using the following procedure.
Caution
Front panel settings affect only the UPS Unit on which they are made (the other UPS
Units are not affected). However, the same settings should be made on all UPS Units.
① During inverter or standby operation, press CLEAR
UPS status
"Beep beep・・・・" beeper sound
Setting mode
INPUT (green) blinking
BATT.LOW (red) blinking
(Status depends on settings)
② The blinking pattern of the upper four LEDs now indicates the item to be set
( § 12.2.1 to § 12.2.8), selected by pressing
The blinking position changes each time you press
necessary to select the item to set.
UPS status
The beeper sounds once at each
press.
The pattern of blinking upper LEDs
changes.
for at least 3 seconds.
CLEAR
briefly (less than 3 seconds).
- 30 -
Hold for at least 3
seconds
CLEAR , so press it as
Press momentarily