6. Carrying and Installation

Each UPS Unit weighs about 19 kg (41.89 lbs), and the UPS Power Distribution
Unit weights about 7 kg (15.43 lbs).
Install the UPS on a stable surface that can bear the weight of all units.
This surface should be flat, so the UPS cannot fall and cause bodily injury.
The possibility of vibration and shock should be minimized at the
installation location.
CAUTION
Be careful to avoid lower back strain when carrying and installing.
The UPS might fall or be dropped during relocation or installation. Always
hold the UPS Units securely by the upper corners. Bodily injury could result
if a UPS falls to the floor.
◆ 6.1

Environment

Do not install the UPS in the following locations:
Where the ambient temperature exceeds 40°C (104°F).
For optimum battery life, install the UPS where ambient temperature stays between
20 and 25°C (68 and 77°F ).
Where high humidity may occur.
Where corrosive gas or salt spray may be present.
Where it may be subject to vibration and shock.
Where dust may accumulate.
◆ 6.2

Carrying

Carry the UPS within its packing cartons,
removing only when near the installation
location.
• To avoid bodily injury from dropping a UPS
Unit, do not tilt it more than specified
degrees to either side when moving it. Take
CAUTION
preventative measures to avoid dropping a
UPS if it must be tilted more than specified
degrees when moving it.
Equipment type name
Angle of inclination
(degree)
◆ 6.3

Installation

The UPS is designed to be installed either
horizontally in a rack or vertically on the floor.
When installed vertically, the left side (as viewed
from the front) should always be the lower side
(with the control panel at the upper side), and
the coupling brackets should be installed.
Provide the following space around the UPS
system.
At least 20 cm(7.88in) at the front
as air intake space for the cooling fan.
At least 20 cm (7.88in) at the back as air
exhaust space for the cooling fan.
At least 1 meter(39.4in) at the front and 50 (19.69in)cm at the back for maintenance
when needed
At least 1 meter(39.4in) from CRT displays to allow for slight leakage of magnetic
flux. Allow some space from devices which might be affected by magnetic flux.
No. of Parallel-Connected UPS Units
2 Units
3 Units
4 Units
30
40
50
5 Units
55
- 12 -
Maintenance space
At least 50cm(19.69in)
Exhaust space
At least 20cm (7.88in)
ASE
Front
Intake space
At least 20cm(7.88in)
Maintenance space
At least 1 m(39.4in)