Step 2:
Set I/O module to the initial state
Every new module has the factory default settings (as figure 1) for user's convenient use.
If you use an old one and you don't know the configuration of the module, please set
the I/O module to the initial state (as figure 2).
The Factory Default Settings :
I/O Module
Address
Baud rate
Checksum
Protocol
The Initial Settings:
I/O Module
Address
Baud rate
Checksum
Protocol
HOWTO: Initialize the I/O module
*I-7000: To set I-7000 module to the initial state, please wire the INIT* to GND (if there is a DIP
switch on the back of it, just set the switch to "INIT" position) and power on the module.
Then the module will become initial state.
*I-87K:
To set I-87K module to the initial state, please set the related DIP Switch on the
I-87K4/5/8/9 I/O expansion unit. For example, change DIP-1 to "ON" and restart the
power, the I/O module in the first slot will become initial state.
Note:
If you use I-87K9 or I-87K5 I/O expansion unit, the DIP-1 is corresponding to the second
slot, so do not use the first slot.
Following, we would like to use I-87K I/O module as an example to show how to serch and
configure with DCON Utility.
3-18
I-7000
1
9600
Disabled
DCON Protocol
(I-7000 & M-7000)
DCON Protocol
Getting Started: PAC-5007/5107/5207/5307 Ver. 1.1, 12/2011
M-7000
1
9600
Not defined
Modbus Protocol
7000 Series
0
9600
Disabled
I-87K
1
115200
Disabled
DCON Protocol
I-87K Series
0
115200
Disabled
DCON Protocol