Technical Data - Dantherm 3000 Service Manual

Dc air conditioner
Table of Contents

Advertisement

Technical data

Introduction

Technical data

a
28
This section covers technical data and dimensions for DC Air Conditioner 3000.
This table shows the technical data for the DC Air Conditioner 3000
Specification
Operational temperature range
Storage temperature
Storage relative humidity
Noise level, outside 2m distance at 35°C internal and
35°C ambient
Protection from dust, water and wind driven rain ac-
cording to EN 60529
Refrigerant / amount
CE, RoHS, UL, c UL and WEEE compliant
Cooling capacity at 35°C internal and 35°C ambient
Internal airflow
External airflow
Power consumption at 35°C internal and 35°C ambient
Efficiency ratio at 35°C internal and 35°C ambient
Input voltage range
Colour
Net weight
Unit illustration (Fig. 9) with dimension to be found on next page
Unit
Value
°C
-15 ~ +55
°C
-40~70
RH%
5~80
dB(A)
65
IP Class 2
55
Type/Kg
R134a / 0,9
Yes
W
3000
m³/h
950
m³/h
1250
W
1000
COP
3
V DC
45-57
RAL
7035
kg
63
Continued overleaf