Models Covered By This Manual; Model Identification; General Performance Data - Dantherm CS030040A Product Information Manual

Panel mounted air conditioners usacg-6 control
Table of Contents

Advertisement

Air Conditioner 4000 Installation, Operating & Maintenance Manual

3 MODELS COVERED BY THIS MANUAL

3.1

Model Identification

The model numbering format is detailed below.
C = CLASSIC
CS030040A-H012
Example Number Translation
Classic 30 with Standard Construction
4,000 Btu/Hr-115V 1Ph 50/60Hz
Includes a 1200 Watt Heater Option
3.2

General performance Data

BTU/Hr
Model #
CS030040A-H012
4000
CS030040B-H015
4000
** Rating capacity shown based on 95F return air temperature to cabinet in 95F ambient conditions at
nominal voltage and unimpeded resistance to air flow.
AC-4 CS030040 4K Manual Rev D
S = Standard Configuration
030 = Height of Unit 30"
040 = 4000 BTU/HR
Watts
Removal
Voltage
**
**
1172
115V
1172
230V
A = 115 Volt 1/Phase 60 Hz
B = 230 Volt 1/Phase 50/60 Hz.
Option Codes
H012 = Heater rating = 1200W
F1 = Filter
L = Attachment Plug
P_ _ = Paint: Requires an additional 2 digits to refer
to color of paint
Cooling
Hz
Ph
Current
Amps
60
1
10.9
50/60
1
5.0
Heating
Approx.
Current
Weight
Amps
(lbs/Kg)
10.5
100/45
6.5
100/45
Page 4 of 17