Technical data DFC 350

Introduction
Air flow and sound This table shows the technical data for airflow and sound pressure:

Cabinet

Fan motor
Filter
10
This Free Cooling unit is very compact, quiet and economic due to the Displacement
Free Cooling system. In this product the EC-fan signal is reduced to 5V to get the opti-
mized performance.
Parameter
Max air flow
Max air flow
Free cooling capacity at Δt=5°C
Max power consumption
Sound pressure at 5m from shelter
Sound pressure at 10m from shelter
This table shows the specifications for the cabinet:
Specification
Weight
Metal sheet material
This table shows the data for the fan motor:
Voltage version
Voltage nominal
Current
Max power consumption at standard settings
Speed
This table shows the data for the filter:
Type

Filter Class

Total Area
Recommended filter monitor settings
48V DC
3
514 m
/h
143 l/s
3 kW
40 W
36 dB(A)
31 dB(A)
Designation
Controller included
Aluzinc AZ150
Specification
230V AC
3
514 m
/h
143 l/s
3 kW
35 W
34 dB(A)
31 dB(A)
DFC 350
10 kg
0,8-1,5 mm
48V DC
230V AC
48V DC
230V AC
2,3 A
0,9 A
40 Watt
35 Watt
1500 rpm
1500 rpm
Filter data
Bag filter
F6
2
1,4 m
150 Pa