Preventive maintenance
Introduction
Preventive maintenance has to be carried out to:
The factory warranty is only valid if documented preventive maintenance has been car-
ried out, with an time interval of:
A written log at site is adequate documentation for preventive maintenance.
Caution
Disconnect any supply before working on the unit
Make sure that all work has been performed correctly before switching power back
Cleaning
The unit must be cleaned according to the recommended preventive maintenance plan.
Tools required:
Phase
Anticipate a continues operation in product expected lifetime of 10 years or more
Meet the warranty conditions
Avoid malfunctions
Avoid inefficient operation
Maximize the unit's lifetime
Maximum 6 months when unit is located in normal air quality environment
Maximum 2 months when unit is located in bad quality air environment
on
Vacuum cleaner or compressed air
Soft brush
TX20 screwdriver
NHR-60 cleaning agent if it´s very dirty
1
Open the units outside cover
2
Clean the condenser
3
IF the coils still dirty, please apply NHR-60 cleaning agent on coil fins, and
after 5 minutes rinse gently with water, WITHOUT spraying water on any elec-
trical parts
4
Perform end inspection according inspection list below
Description
Continued overleaf
17