Start-Up, Calibration And Operation Of The Burner; Notes On Safety For The First Start-Up; Adjustments Prior To Ignition; Burner Start-Up - Riello 3898350 Installation, Use And Maintenance Instructions

Forced draught gas burners
Table of Contents

Advertisement

6

Start-up, calibration and operation of the burner

6.1

Notes on safety for the first start-up

The first start-up of the burner must be carried out
by qualified personnel, as indicated in this manual
and in compliance with the standards and regula-
WARNING
tions of the laws in force.
6.2

Adjustments prior to ignition

Combustion head adjustment is already described on page 20.
In addition, the following adjustments must also be made:
 open manual valves upline from the gas train.
 Adjust the minimum gas pressure switch to the start of the
scale.
 Adjust the maximum gas pressure switch to the end of the
scale.
 Adjust the air pressure switch to the start of the scale.
 Purge the air from the gas line.
We recommend using a plastic tube routed outside the build-
ing and to purge air until gas is smelt.
 Fit a U-type pressure gauge or a differential pressure gauge
(Fig. 24), with socket (+) on the gas pressure of the pipe
coupling and (-) in the combustion chamber.
The manometer readings are used to calculate MAX burner
output using the Tab. J.
 Connect two lamps or testers to the two gas line solenoids to
check the exact moment in which voltage is supplied. This
operation is unnecessary if each of the two solenoids is
equipped with a pilot light that signals voltage passing
through.
Configure the Inverter according to the manual
and the instructions supplied.
WARNING
6.3

Burner start-up

Close all consents and safety devices and put the selector to po-
sition "AUTO" (Fig. 25).
Select the "MANUAL" mode (for further information refer to the
relevant control box manual).
Make sure that the lights or testers connected to
the solenoids, or the pilot lights on the solenoids
themselves, indicate that no voltage is present.
WARNING
If voltage is present, stop the burner immediately
and check the electrical connections.
6.4

Burner ignition

Once the above steps are complete, the burner should light.
If the motor starts up, but the flame does not appear and the con-
trol box goes into lockout, reset it and wait for a new ignition at-
tempt.
If ignition does not occur, it may be that gas is not reaching the
combustion head within the safety time period of 3 seconds. In
this case, increase gas ignition delivery.
The arrival of gas at the pipe coupling is indicated by the U-type
pressure gauge (Fig. 24).
Start-up, calibration and operation of the burner
Check the correct working of the adjustment, com-
mand and safety devices.
WARNING
Before starting up the burner, it is good practice to
adjust the gas train so that ignition takes place in
conditions of maximum safety, i.e. with gas deliv-
ery at the minimum.
CAUTION
D3650
Once the burner has ignited, proceed with the global adjustment
of the burner.
Once regulations have been made, select the "AUTOMATIC"
mode on the AZL display.
25
GB
20065570
Fig. 24
Fig. 25
20041914