Electrical wiring

Notes on safety for the electrical wiring
 The electrical wiring must be carried out with the electrical supply disconnected.
 Electrical wiring must be made in accordance with the regulations currently in force in the country of destination
and by qualified personnel. Refer to the wiring diagrams.
 The manufacturer declines all responsibility for modifications or connections different from those shown in the wir-
DANGER
ing diagrams
 Check that the electrical supply of the burner corresponds to that shown on the identification label and in this man-
ual.
 The burner has been type-approved for continuous use.
This means they should compulsorily be stopped at least once every 72 hours to enable the control box to per-
form checks of its own start-up efficiency. Normally, burner stopping is guaranteed by the boiler's thermostat/pres-
sure switch.
 If this is not the case, a time switch should be fitted in series to TL to stop the burner at least once every 72 hours.
Refer to the wiring diagrams.
 The electrical safety of the device is obtained only when it is correctly connected to an efficient earthing system,
made according to current standards. It is necessary to check this fundamental safety requirement. In the event of
doubt, have the electrical system checked by qualified personnel. Do not use the gas tubes as an earthing system
for electrical devices.
 The electrical system must be suitable for the maximum power absorption of the device, as indicated on the label
and in the manual, checking in particular that the section of the cables is suitable for that level of power absorp-
tion.
 For the main power supply of the device from the electricity mains:
- do not use adapters, multiple sockets or extensions;
- use a multiple pole switch with at least a 3 mm gap between the contacts (overvoltage category III), as envis-
aged by the present safety standards.
 Do not touch the device with wet or damp body parts and/or in bare feet.
 Do not pull the electric cables.
Before carrying out any maintenance, cleaning or checking oper-
ations:
Disconnect the electrical supply from the burner
by means of the main system switch.
DANGER
Close the fuel interception tap.
DANGER
Avoid condensate, ice and water leaks from form-
ing.
DANGER
If the hood is still present, remove it and proceed with the electri-
cal wiring according to the wiring diagrams.
Use flexible cables in compliance with the EN 60 335-1 standard.
20041914
Installation
5.12.1 Supply cables and external connections
passage
All the cables to be connected to the burner must be threaded
through cable grommets. The use of the cable grommets can
take various forms. By way of example see Fig. 23.
2
7
8
7
7
20122840
Key (Fig. 23)
1
Electrical supply
2
Regulating probes
3
Minimum gas pressure switch
4
Pressure switch kit for PGVP gas valve leak detection
5
Gas train
6
Consents / Safety
7
O
kit probes and O
2
8
Motor revolution sensor
9
Available
Perform all maintenance, cleaning or inspection
operations and mount the casing again.