4 | Technical data
4.1.4 Electrical operating conditions
4.1.4.1 Device classification
Requirement
Overvoltage category
Pollution degree
4.2 Electrical data
4.2.1 Fuse protection according to
4.2.2 Fuse protection according to UL Class J
4.2.3 Fuse protection according to UL type gR / aR
14
Standard
EN 61800-5-1
EN 60664-1
Rated input voltage
Rated input voltage (UL)
Input voltage range
Peak input voltage
Mains phases
Mains frequency
Mains form
Leakage current according to EN 60939-1:
2010 (Annex A9)
Rated input current
Rated input current (UL)
Overload (60s)
Power dissipation
Construction and protection class
Suitable KEB housing size
The following table shows the maximum fuse size of the
and an input voltage of 400 V. In case of other dimensioning, the values must be de-
signed for the current and the
12E6T60-3000
Tab. 1: Fuse protection according to
The following table shows the maximum fuse size of the type
1:1 dimensioning and an input voltage of 480 V. In case of other dimension-
ing, the values must be designed for the current and the
downstream drive controller.
12E6T60-3000
in Vorbereitung
Tab. 2: Fuse protection according to UL Class J
Class
Notes
III
-
2
Non-conductive pollution, occasional condensa-
tion when
PDS
12E6T60-3000
400 V
480 V
0...528 V
550 V für max. 1 min/h
3
50/60 Hz ±2 Hz
TN, TT, IT
0,8 mA @ 400 V; 1,0 mA @ 480 V
840 A
744 A
150 %
110 W
IP00
F6 / 9
SCCR
rating of the downstream drive controller.
SCCR 30kA
-
SCCR 5kA
SCCR 10kA
in Vorbereitung
KEB Automation KG
is out of operation.
type gG
with a 1:1 dimensioning
SCCR 100kA
2 x 450 A
Class J
SCCR
rating of the
SCCR 18kA
in Vorbereitung
ma_dr_e6-hf-filter-nb-20337731_en