Start Sequence; Introduction - Watts Aerco Benchmark OMM-0124 Installation And Start-Up Manual

Natural gas, propane gas and dual fuel fired modulating & condensing boilers
Table of Contents

Advertisement

Benchmark 5000-6000 Boiler Installation & Startup Manual
SECTION 3: START SEQUENCE
SECTION 3: START SEQUENCE

3.1 INTRODUCTION

The information in this section provides a guide to starting the Benchmark Boiler using the C-
More Controller, which is mounted on the front of the unit. It is imperative that the initial startup
of this unit be performed by factory trained personnel. Operation prior to initial startup by factory
trained personnel may void the equipment warranty. In addition, the following WARNINGS and
CAUTIONS must be observed at all times.
WARNING!
Electrical voltages in this system include 120, 208, 460, 575 and 24 volts AC. It must be
serviced only by factory certified service technicians.
Do not attempt to dry fire the unit. Starting the unit without a full water level can
seriously damage the unit and may result in injury to personnel or property damage. This
situation will void any warranty.
CAUTION!
All of the installation procedures in Section 2 must be completed before attempting to start
the unit.

3.2 START SEQUENCE

When the C-More Controller's ON/OFF switch is set to the ON position, it checks all pre-purge
safety switches to ensure they are closed. These switches include:
Safety Shut-Off Valve (SSOV) Proof of Closure (POC) switch
Low Water Level switch
High Water Temperature switch
High Gas Pressure switch
Low Gas Pressure switch
NOTE:
The Blocked Inlet and downstream Blower Proof switches are not checked prior to starting
the pre-purge.
If all of the above switches are closed, the READY light above the ON/OFF switch will light and
the unit will be in the STANDBY mode.
NOTE:
If any of the Pre-Purge safety device switches are open, the appropriate fault message will
be displayed. Also, the appropriate messages will be displayed throughout the start
sequence, if the required conditions are not observed.
OMM-0123_E • GF-207 • 12/17/2019
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
Page 37 of 95