SECTION 2: INSTALLATION
PUMP RELAY
The Benchmark pump relay (SPDT) contact is rated for:
10 A Resistive @ 277 VAC/28 VDC
1/3 HP N/O @ 120/240 VAC
1/6 HP N/C @ 120/240 VAC
480 VAC Pilot Duty @ 240-277 VAC Pilot Duty
Figure 2-16: Schematic – System Pump Start using Boiler Pump Relay
If pump/valve load exceeds the above contact ratings, use a separate contact relay, as shown in
Figure 2-17.
Figure 2-17: Schematic – System Pump Start using a Separate Contact Relay
OMM-0123_E • GF-207 • 12/17/2019
Figure 2-15: Pump Relay Location
(Orange) – N/O
(Yellow) - COM
Pump Relay Terminals
Heating Pump
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
POWER BOX
(Orange) – N/O
(Yellow) - COM
Pump Relay Terminals
Heating Pump
Contact Relay
(Supplied by Others)
N
POWER PUMP(S) FROM
INDEPENDENT FUSED
CIRCUITS
H
Page 33 of 95