Watts Aerco Benchmark OMM-0124 Installation And Start-Up Manual page 64

Natural gas, propane gas and dual fuel fired modulating & condensing boilers
Table of Contents

Advertisement

Benchmark 5000-6000 Boiler Installation & Startup Manual
SECTION 5: SAFETY DEVICE TESTING
LOW Gas Pressure Test Instructions
7. Open the external gas supply ball valve upstream of the unit.
8. Place the unit in MANUAL mode and adjust the Air/Fuel Valve position (% open) to 100%.
9. While the unit is firing, read the CO value on the combustion analyzer and slowly decrease
the incoming gas supply pressure until the CO reading is approximately 300 ppm.
10. Take a reading of the inlet gas pressure. If the inlet pressure is below the minimum
calculated in step 5, above, then increase the pressure to match the calculated minimum.
11. Slowly turn the indicator dial on the Low Gas Pressure switch until the unit shuts down
due to a gas pressure fault.
12. Readjust the inlet gas pressure to what it was prior to the test.
13. Press the CLEAR button on the Control Panel to clear the fault.
14. The fault message should clear and the FAULT indicator should go off. The unit should
now restart.
15. For Dual Fuel units, repeat the previous procedure on the PROPANE gas train, starting
with the PROPANE Low Gas Pressure Switch, shown in the bottom-half of Figure 5-1.
TO
AIR/FUEL
VALVE
MANUAL
SHUT-OFF
VALVE
Dual Fuel gas train showing both Natural Gas and
Figure 5-1: Low Gas Pressure Switch Locations & Test Ports
OMM-0123_E • GF-207 • 12/17/2019
Propane gas trains
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
Alternative location for manometer
if hose barb is preferred
NATURAL GAS Low Gas
Pressure Test Port
Install manometer here
Alternative
location
PROPANE Low Gas
Pressure Test Port
Install manometer here
Page 64 of 95