SECTION 6: BOILER SEQUENCING TECHNOLOGY
6.3.3 OPTION 3 - Outdoor Reset With Direct Wired Header Sensor
And Direct Wired Outdoor Sensor
OPTION 3 - Outdoor Reset With Direct Wired Header Sensor And Direct Wired
Outdoor Sensor Instructions
NOTE:
Both Header Sensor AND Outdoor Sensor must be wired. See the C-More Controller User
Manual, OMM-0032 (GF-112) and ProtoNode User Manual, OMM-0080 (GF-129) for more
information.
Step 1 - Direct Wired Header Sensor Wiring
On the MANAGER Unit, connect the Header Temperature Sensor (P/N 61040) to the Feed
1.
Forward (FFWD) terminals on the P-1 Harness Via the terminal block labeled Header Temp
sensor in the I/O Box.
NOTE:
The header sensor must be installed between 2 and 10 (0.61 and 3.1m) feet downstream of
the LAST boiler in the plant's supply water header. Shielded pair 18 - 22 AWG cable is
recommended for header sensor wiring. There is no polarity to be observed. The ground for
the shield is at the "SHLD" terminal in the I/O the Box. The sensor end of the shield must be
left free and ungrounded.
TEMP SENSOR P/N 61040
Step 2 - Direct Wired Outdoor Sensor
On the MANAGER Unit, Connect the Outdoor Temperature Sensor (P/N 61047) to the
1.
"OUT" and "COM" terminals in the I/O Box.
NOTES:
Twisted shielded pair 18 - 22 AWG cable is recommended for header sensor wiring.
There is no polarity to be observed. The ground for the shield is at the "SHLD" terminal
in the I/O the Box. The sensor end of the shield must be left free and ungrounded.
When mounting the Outdoor sensor, it must be located on the North side of the building
where an average outside air temperature is expected. The sensor must be shielded
from direct sunlight as well as impingement by the elements. The outdoor sensor may
be wired up to 200 feet (61m) from the boiler.
TEMP SENSOR P/N 61047
OMM-0123_E • GF-207 • 12/17/2019
HEADER TEMP SENSOR
(Continued)
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST