Quick Start Guide
00825-0300-4728, Rev BA
January 2016
Rosemount
644H Temperature
Transmitters
®
with PROFIBUS
PA

Advertisement

loading

Summary of Contents for Emerson Rosemount 644H

  • Page 1 Quick Start Guide 00825-0300-4728, Rev BA January 2016 ™ Rosemount 644H Temperature Transmitters ® with PROFIBUS...
  • Page 2: Table Of Contents

    January 2016 Quick Start Guide NOTICE This guide provides basic guidelines for the Rosemount 644. It does not provide instructions for detailed configuration, diagnostics, maintenance, service, troubleshooting, or installation. Refer to the 644 Reference Manual (document number 00809-0100-4728) for more instruction. The manual and this guide are also available electronically on www.rosemount.com.
  • Page 3: Mount The Transmitter

    Quick Start Guide January 2016 1.0 Mount the transmitter Mount the transmitter at a high point in the conduit run to prevent moisture from draining into the transmitter housing. 1.1 Typical connection head installation Head mount transmitter with DIN plate style sensor 1.
  • Page 4: Wire And Apply Power

    January 2016 Quick Start Guide 4. Pull the sensor wiring leads through the universal head and transmitter. Mount the transmitter in the universal head by threading the transmitter mounting screws into the universal head mounting holes. 5. Mount the transmitter-sensor assembly into the thermowell. Seal adapter threads with silicone tape.
  • Page 5 4-wire RTD and and mV ™ 1. Emerson Process Management provides 4-wire sensors for all single element RTDs. Use these RTDs in 3-wire configurations by leaving the unneeded leads disconnected and insulated with electrical tape. 2. The transmitters must be configured for at least a 3-wire RTD in order to recognize an RTD with a compensation loop.
  • Page 6: Ground The Transmitter

    January 2016 Quick Start Guide Note • Each segment in a PROFIBUS trunk must be terminated at both ends. • Some DP/PA couplers contain the power supply, one terminator, and the power conditioner within the coupling device. • The configuration tool is typically located in the control room. 2.3 Ground the transmitter Ungrounded thermocouple, mV, and RTD/ohm inputs Each process installation has different requirements for grounding.
  • Page 7 Quick Start Guide January 2016 Note Connect shields together, electrically isolated from the transmitter Option 3 1. Ground sensor wiring shield at the sensor, if possible. 2. Ensure the sensor wiring and signal wiring shields are electrically isolated from the transmitter housing. 3.
  • Page 8: Verify Tagging

    January 2016 Quick Start Guide 3.0 Verify tagging 3.1 Commissioning (paper) tag To identify which device is at a particular COMMISSIONING TAG location use the removable tag provided IDENT_NUMBERS 4153 [9700] with the transmitter. Ensure the physical Device Address: ## device tag (PD Tag field) is properly Physical Device Tag: TT- 100 entered in both places on the removable...
  • Page 9: January

    Quick Start Guide January 2016 Note When shipped from the factory Rosemount 644 PROFIBUS Profile 3.02 devices are defaulted in Identification Number ADAPTATION MODE. This mode allows the transmitter to communicate with any Profibus control host with either the generic Profile GSD file (9700) or the Rosemount 644 specific GSD (4153) loaded in the host;...
  • Page 10 January 2016 Quick Start Guide Table 2. AI Block Parameters Parameter Comments The CHANNEL parameter defines which transducer block measurement is used by CHANNEL the AI block. In the 644 Transmitter, the channel will always be set to Sensor 1. There is no other option for this variable.
  • Page 11: Product Certifications

    Quick Start Guide January 2016 Product Certifications Rev 1.4 5.0 European Directive Information A copy of the EC Declaration of Conformity can be found at the end of the Quick Start Guide.The most recent revision of the EC Declaration of Conformity can be found at www.rosemount.com 6.0 Ordinary Location Certification As standard, the transmitter has been examined and tested to determine that the design...
  • Page 12 January 2016 Quick Start Guide Certificate: 3044581 [Headmount HART] Standards: FM Class 3600: 2011, FM Class 3610: 2010, FM Class 3611: 2004, FM Class 3810: 2005, ANSI/NEMA - 250: 1991, ANSI/IEC 60529: 2004; ANSI/ISA 60079-0: 2009; ANSI/ISA 60079-11: 2009 Markings: [No Enclosure]: IS CL I, DIV I, GP A, B, C, D T4; CL I ZONE 0 AEx ia IIC T4 Ga; NI CL I, DIV 2, GP A, B, C, D T5[With Enclosure]: IS CL I / II / III, DIV 1, GP A, B, C, D, E, F, G;...
  • Page 13 Quick Start Guide January 2016 I1 ATEX Intrinsic Safety Certificate: [Headmount HART]: Baseefa12ATEX0101X [Headmount Fieldbus/PROFIBUS]: Baseefa03ATEX0499X [Railmount HART]: BAS00ATEX1033X Standards: EN 60079-0: 2012, EN 60079-11: 2012 Markings: [HART]: II 1 G Ex ia IIC T6…T4 Ga; [Fieldbus/PROFIBUS]: II 1 G Ex ia IIC T4 Ga; Table 5 for Entity Parameters and Temperature Classifications.
  • Page 14 January 2016 Quick Start Guide International E7 IECEx Flameproof Certificate: IECEx FMG 12.0022X Standards: IEC 60079-0: 2011, IEC 60079-1: 2007 Markings: Ex d IIC T6…T1 Gb, T6(-50 °C ≤ T ≤ +40 °C), T5…T1(-50 °C ≤ T ≤ +60 °C); Table 4 for process temperatures.
  • Page 15 Quick Start Guide January 2016 NK IECEx Dust Certificate: IECEx FMG 12.0022X Standards: IEC 60079-0: 2011, IEC 60079-31: 2008 Markings: Ex tb IIIC T130 °C Db, (-40 °C ≤ T ≤ +70 °C); IP66 Table 4 for process temperatures. Conditions of Certification (X): 1.
  • Page 16 January 2016 Quick Start Guide China E3 China Flameproof Certificate: GYJ111385 Standards: GB3836.1-2000, GB3836.2-2000, GB12476.1-2000 Markings: Ex d IIC T6; DIP A20 T 95 °C; IP66 Special Conditions for Safe Use (X): 1. Temperature Assembly using temperature sensor type 65, 68, 75, 183, 185 are certified.
  • Page 17 Quick Start Guide January 2016 Special Conditions for Safe Use (X): 1. The ambient temperature range is: For 644 Fieldbus, PROFIBUS, and Legacy 644 HART Max input power: Transmitter output T code Ambient temperature -60 °C ≤ T ≤ +40 °C 0.67 -60 °C ≤...
  • Page 18 January 2016 Quick Start Guide For Enhanced 644 HART: Terminals of power supply (+, -) Max internal Max input Max input Max input parameters: voltage: current: power: (mA) (nF) (mH) ≤ +80 °C) 150 (T ≤ +70 °C) 170 (T 0.67/0.8 ≤...
  • Page 19 Quick Start Guide January 2016 N3 China Type n Certificate: GYJ101421 Standards: GB3836.1-2000, GB3836.8-2003 Markings: Ex nA nL IIC T5/T6 Special Conditions for Safe Use (X): 1. The relation among T code, ambient temperature range is as following: For 644 Fieldbus, PROFIBUS, and Legacy 644 HART: T code Ambient temperature -40 °C ≤...
  • Page 20 January 2016 Quick Start Guide Japan E4 Japan Flameproof Certificate: TC20671 [J2 with LCD], TC20672 [J2], TC20673 [J6 with LCD], TC20674 [J6] Markings: Ex d IIC T5 Combinations K1 Combination of E1, I1, N1, and ND K2 Combination of E2 and I2 K5 Combination of E5 and I5 K7 Combination of E7, I7, and N7 KA Combination of K6, E1, and I1...
  • Page 21 Quick Start Guide January 2016 7.1 Tables Table 4. Process Temperatures T130 Max Ambient +40 °C +60 °C +60 °C +60 °C +60 °C +60 °C +70 °C Transmitter with LCD display 0” 55 °C 70 °C 95 °C 95 °C 95 °C 95 °C 95 °C...
  • Page 22 January 2016 Quick Start Guide Figure 3. Rosemount 644 Declaration of Conformity...
  • Page 23 Quick Start Guide January 2016...
  • Page 24 January 2016 Quick Start Guide...
  • Page 25 Quick Start Guide January 2016...
  • Page 26 January 2016 Quick Start Guide...
  • Page 27 Quick Start Guide January 2016...
  • Page 28 Enquiries@AP.EmersonProcess.com Standard Terms and Conditions of Sale can be found at www.Emerson.com/en-us/pages/Terms-of-Use.aspx Middle East and Africa Regional Office The Emerson logo is a trademark and service mark of Emerson Emerson Process Management Electric Co. Emerson FZE P.O. Box 17033, AMS, Rosemount and Rosemount logotype are trademarks of Jebel Ali Free Zone - South 2 Emerson Process Management.