PREPARATION FOR INSTALLATION
The following preparation must be carried out before the gas fi re can be installed.
1.5.1
Instructions for positioning the outlet
1.5.1.1 Positioning the outlet for correct operation:
Roof-mounted outlet:
Figure 1: Roof-mounted outlet
This must be positioned at least 0.5 m from the roof edge;
the apex of the roof can be disregarded.
Wall-mounted outlet:
Figure 2: Wall-mounted outlet
This must be positioned at least 0.5 m from:
• the corner of the building.
• the roof overhang, the rain gutter.
• balconies etc., unless the exhaust construction
extends to at least the face of the protruding section.
Installation instructions
>0.5 m
>0.5 m