2.1.3 Grounding

Proper grounding of this system is a requirement. To be effective, ground connections should be made with a minimum 12
AWG, 600 volt insulated wire to a ground point within 10 feet of the telephone entry system. The ground point must be at an
electrical panel, a metallic cold water pipe that runs in the earth, or a stainless steel grounding rod driven at least ten (10) feet
into the soil. A architectural style mounting post anchored to concrete does NOT make a good ground.
Ground to an existing electrical system.

2.1.4 Surge Suppression

The use of surge suppressors can significantly reduce the chance of component failure because of static charges or surges.
DoorKing recommends Installing a Phone Line surge suppressor (DoorKing P/N 1877-010 or equivalent) and a Low Voltage
surge suppressor (DoorKing P/N 1878-010 or equivalent) to help protect the entry system from power surges.
Phone Company
Install on each
16.5 VAC Transformer

2.1.5 Expansion Boards and Elevator Control

If Expansion Boards are being used with this system, refer to the Installation and Wiring manual that came with the Expansion
boards, for detailed information on wiring Expansion boards to the PC programmable telephone entry system.
If Elevator Control is used with this system, refer to the Elevator Control Installation and Wiring manual for detailed information
on wiring the elevator control boards to this system and to the elevator push button control panel.

2.1.6 Ferrite Filter

The Telephone Entry System comes with two (2) Ferrite Filters. These will help
prevent noise and hum pickup in the phone lines. One is installed around the 16 VAC
power wires on the main terminal #19 and #20. The second is installed around all the
wires connected to the aux terminal.
l
i n a
e r m
C
1 6 A
i n T
C
1 6 A
B A T
M a
1 N O
1 N C
2 R Y
2 C
2 0
1 9
1 8
Power Wires
1 7
1 6
1 5
on all models
1 4
18
Some Acceptable Ground Sources
Ground
Wire
Ground to a metallic cold water pipe.
Phone Line Surge Suppressor
1877-010
Surge suppressor within 3 ft of ground source.
Low Voltage Surge Suppressor
1878-010
Surge suppressor within 3 ft of ground source.
C l i
p R
#1
e l e
a s e
To install the ferrite filter, release the
clip on the side to open the filter,
place the wires in the circular core
and snap the filter closed.
Phone line surge suppressor
within 10 ft of entry system.
PHONE LINE
Low voltage surge suppressor
within 10 ft of entry system.
POWER LINE
IMPORTANT:
Ground wire shown without
safety protection for clarity. Make sure
ground wire is protected from being
touched or electrical shock could occur!
Ground
Wire
Grounding rod 10 feet in soil.
Auxiliary Wires
A
Z
CALL
A
Z
CALL
#2
C l i
p R
e l e
a s e
1835-065-D-5-17

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents