General Specifications - Omron sysmac NX Series User Manual

Machine automation controller system units
Hide thumbs Also See for sysmac NX Series:
Table of Contents

Advertisement

2 Specifications
2-1

General Specifications

This table shows the general specifications of all System Units.
Enclosure
Grounding methods
Operat-
Ambient operating temper-
ing en-
ature
viron-
Ambient operating humidi-
ment
ty
Atmosphere
Ambient storage tempera-
ture
Altitude
Pollution degree
Noise immunity
Overvoltage category
EMC immunity level
Vibration resistance
Shock resistance
Insulation resistance
Dielectric strength
Applicable standards
Note 1. The specifications of insulation resistance and dielectric strength vary with NX Unit Models.
Note 2. Refer to the OMRON website (www.ia.omron.com) or ask your OMRON representative for the most re-
cent applicable standards for each model.
2-2
Item
Mounted in a panel
Ground of 100 Ω or less
0 to 55°C
10 to 95% RH (with no icing or condensation)
Must be free from corrosive gases.
-25 to 70°C (with no icing or condensation)
2,000 m max.
Pollution degree 2 or less: Conforms to JIS B 3502 and IEC 61131-2.
Conforms to IEC 61000-4-4, 2 kV (power supply line)
Category II: Conforms to JIS B 3502 and IEC 61131-2.
Zone B
Conforms to IEC 60068-2-6.
5 to 8.4 Hz with amplitude of 3.5 mm,
8.4 to 150 Hz, acceleration of 9.8 m/s
100 min each in X, Y, and Z directions (10 sweeps of 10 min each =
100 min total)
Conforms to IEC 60068-2-27, 147 m/s
directions
Refer to the individual specifications of NX Units.
Refer to the individual specifications of NX Units.
cULus: Listed (UL508), ANSI/ISA 12.12.01, EU: EN 61131-2, C-Tick,
KC (KC Registration), NK, and LR
Specification
2
2
, 3 times each in X, Y, and Z
NX-series System Units User's Manual (W523)