Omron sysmac NX Series User Manual page 62

Machine automation controller system units
Hide thumbs Also See for sysmac NX Series:
Table of Contents

Advertisement

3 Part Names and Functions
Let-
ter
(A)
Terminal number indi-
cations
(B)
Release holes
(C)
Terminal holes
(D)
Ground terminal mark
The NX-TB£££2 and NX-TB£££1 Terminal Blocks have different terminal current capacities.
The former has 10 A and the latter has 4 A.
To differentiate between the two models of terminal blocks, use the terminal number column indica-
tions. The terminal block with white letters on a dark background is the NX-TB£££2.
You can mount either terminal block to the Units that the current capacity specification of the termi-
nals is 4 A or less.
You can only mount the NX-TB£££2 Terminal Block to the Units that the current capacity specifi-
cation of the terminals is greater than 4 A.
Additional Information
• Each power supply-related Unit is compatible with only one of three types of terminal blocks.
You cannot use a terminal block with a number of terminals that differs from the specifications
for a particular Unit.
• The 8-terminal type does not have terminal holes and release holes for following terminal
numbers.
A2, A4, A6, A8, B2, B4, B6, and B8
 Applicable Terminal Blocks for Each Unit Model
The following indicates the terminal blocks that are applicable to each Unit.
Unit model num-
ber
NX-PD1000
NX-PF0630
NX-PF0730
NX-PC0£££
3-4
Name
Terminal numbers for which A and B indicate the column, and 1 to 8 indicate
the line are displayed.
The terminal number is a combination of column and line, i.e. A1 to A8 and
B1 to B8.
The terminal number indications are the same regardless of the number of
terminals on the terminal block.
Insert a flat-blade screwdriver into these holes to connect and remove the
wires.
The wires are inserted into these holes.
This mark indicates the ground terminals. It is only on the NX-TBC££2.
Model
NX-TBA081
NX-TBC082
NX-TBA081
NX-TBA082
NX-TBA082
NX-TBA161
NX-TBA162
Function
Terminal block
Number of termi-
Ground terminal
nals
8
Not provided
Provided
Not provided
16
NX-series System Units User's Manual (W523)
Current capacity
mark
4 A
10 A
4 A
10 A
4 A
10 A

Advertisement

Table of Contents
loading

Table of Contents