Vertiv™ NetSure™ 7100 Series -48 VDC Power System User Manual
IB2 (Controller Interface Board) and Optional EIB (Controller Extended Interface Board) Replacement
Refer to Figure 3.1 for circuit card location.
Procedure
1.
Performing this procedure may activate external alarms. Do one of the following. If possible, disable these alarms. If these
alarms cannot be easily disabled, notify the appropriate personnel to disregard any future alarms associated with this system
while the procedure is being performed.
DANGER! Performing the next steps exposes service personnel to battery potential. Exercise extreme caution not to
inadvertently contact or have any tool inadvertently contact any energized electrical termination.
2.
Open the distribution cabinet's front door by turning the latch in the counterclockwise position.
WARNING! Damage to the circuit card may result if the next step is not followed.
3.
Connect an approved grounding strap to your wrist. Attach the other end to a suitable ground.
4.
Remove the shield to access the circuit cards at the bottom of the distribution cabinet.
5.
Carefully label the wires connected to the customer connection terminal blocks on the circuit card. These wires must be
connected to the same terminals on the replacement circuit card. Refer to Figure 5.5 or Figure 5.6.
6.
Carefully label the connectors plugged into the circuit card. These connectors must be plugged into the same connectors on
the replacement circuit card. Refer to Figure 5.5 or Figure 5.6.
DANGER! In the next step, external alarm wiring may be energized from an external source. DO NOT allow bare wire ends to
contact any grounded or energized object.
7.
Remove the external wiring from the customer connection terminal blocks. DO NOT allow the bare wire end to contact any
grounded or energized object. Isolate the wire end with electrical tape. Repeat for each wire to be removed.
8.
Unplug all connectors plugged into the circuit card.
9.
Remove the screws securing the circuit card and remove the circuit card from the distribution cabinet.
10.
In this step, ensure you do not intermix the old and replacement circuit cards. Set the switch on the replacement circuit card
to the same setting as the old circuit card. Switch settings are documented in the "Setting Jumpers and Switch Options"
section of the Power System Installation Instructions (IM582127000100).
11.
Slide the replacement circuit card into the mounting position inside the distribution cabinet, and secure with the screws
removed from the old circuit card.
12.
Plug all connectors removed from the old circuit card into the same position on the replacement circuit card.
DANGER! In the next step, external alarm wiring may be energized from an external source. DO NOT allow bare wire ends to
contact any grounded or energized object.
13.
Reconnect the external wiring to the correct terminals on the customer connection terminal block. First remove the electrical
tape that was applied to the bare wire end in a previous step. DO NOT allow the bare wire end to contact any grounded or
energized object. After securing the wire, gently tug on the wire to ensure that it cannot be pulled out of the terminal block.
Repeat for each wire to be reconnected.
14.
Remove the grounding wrist strap.
15.
Close the distribution cabinet's front door. Turn the latch clockwise to secure the door.
16.
Reboot the Controller
Local Menu Navigation: At the Main Screen, press ENT and ESC at the same time to reset the NCU Controller.
Web Menu Navigation: Go to Advance Settings Menu / SW Maintenance Tab / Reboot Controller button.
17.
Enable the external alarms, or notify appropriate personnel that this procedure is finished.