2: View Zone Points - Honeywell SILENT KNIGHT 6700 Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

Zone
Type of Delay
Alternate P.A.S. -
Positive Alarm
2
Sequence
SNGL ILOCK
DBL ILOCK
1
The SK-FIRE-CO and other CO detectors can only be installed in a 1 count zone. They will operate as a 1- count point regardless of the
programmed zone type (i.e. Alarm Verification, 2 count, etc.).
2
PAS operation requires the approval of the local Authority Having Jurisdiction. Alarm Verification, two-count, single interlock releasing, and
double interlock releasing cannot be used while PAS is enabled.
Heat Detector Sensitivity
Use this feature to set the temperature at which high temperature detectors will respond. All detectors in the zone will respond in the same
way.
The range for the SD505-HEAT heat detector is from 135°F to 150°F.
The range for the SK-HEAT-HT heat detector is from 135°F to 190°F.
The SD505-HEAT and SK-HEAT-HT heat detectors are absolute temperature devices. This means that they respond to an alarm immediately
if the temperature in the zone goes above the programmed temperature.
1.
Enter the temperature at which the heat detector will respond. Or use the up or down arrow keys to scroll through the range.
2.
Then press ENTER.
Zone Accessory Options
1.
Login to the panel.
2.
Select 7 to access the Program Menu.
3.
Press 2 to enter the Zone Menu.
4.
Press 1 to edit a zone.
5.
Enter the Zone Number, then press ENTER.
6.
Press 3 to edit the Zone's Accessory options.
Single or Multi-Station cadence pattern (choose from Patterns 00 to 02, 23 if using SK. Choose from 00-16, 23 if using SD devices). See
Appendix C, "Cadence Patterns", on page 121.
CO Single and Multi-station Cadence (choose from Cadence Patterns 00 to 02, 23 for SK devices).
NOTE: The B200S Intelligent Sounder base provides the recommended CO cadence pattern
NOTE: If the SLC protocol is changed from SD to SK series and the cadence is no longer valid for SK, the zone cadence will be set to
constant on.
7.
For Local Zone, (choose Y or N, for Yes or No),
8.3.2 View Zone Points
To view the points in a zone, follow these steps:
1.
Login to the panel. The panel will automatically access the main menu.
2.
Select 7 to access the panel programming.
3.
Press 2 to enter the zone menu.
4.
Press 2 to view the zone points.
6700 Manual — P/N LS10148-001SK-E:F 8/29/2022
An improved version of PAS is available with software version 6.04 or higher, for use with the 6860 and 6855 only.
Existing systems with PAS enabled will still function normally.
The PAS option will program an automatic, addressable detector to delay panel activation (including alarm relay and
communicator) for a period of 15 seconds plus a delay time of up to three minutes. When a detector triggers an alarm,
the onboard piezo sounds immediately, but the mapped output groups (e.g. NACs, control/relay modules) are prevented
from activating for 15 seconds. This inhibit time is factory set and cannot be changed.
Pressing the ACK key during the 15 second inhibit time will start a timer which prevents activation of the mapped output
groups for an additional time duration for up to three minutes and display a countdown for the three minute delay. After
the delay, the mapped output groups will activate if the source of the alarm is not cleared. If a second alarm occurs
during either time delay, the alarm will be processed immediately, causing activation of the appropriate output groups.
If PAS is enabled,
the onboard piezo sounds immediately.
the control panel LCD display will indicate a PAS-alarm event and the active point.
output groups (NACs and control/relay modules) of associated zones will be inhibited from activating for a
factory-set duration of 15 seconds.
pressing the ACK key will start a timer which inhibits output activation for additional time delay of up to three
minutes.
a second alarm occurring at any time during either time delay will cause immediate activation of all associated
outputs.
See Section 9.6.1 for information on the single interlock releasing operation.
See Section 9.6.2 for information on the double interlock releasing operation.
Table 8.2 Alarm Delay Types (Continued)
Description
Programming
77

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents