Honeywell SILENT KNIGHT 6700 Manual page 80

Addressable fire alarm control panel
Table of Contents

Advertisement

Programming
Type
Function
Selection
SK/ SUP
SUP PHOTO DUCT
DETECTOR
SUP SMOKE PHOTO
SUP SMOKE ION
SUP HEAT
SUP ACCLIMATE
SUP HEAT HT
SUP SMOKE
PHOTO/HEAT
SUP SMOKE BEAM
CO SMOKE
ALRM CO/ALRM
DETECTOR
FIRE
SUP CO/ALRM FIRE
ALRM CO/SUP FIRE
SUP CO/SUP FIRE
W-DETECTOR PHOTO
HEAT
PHOTO-HEAT
W-SUP DET
Same as
W-Detector
MAN_PULL
WATERFLOW
SUPERVSY
SWITCH
FIRE DRILL
SILENCE
RESET
PAS_ACK
80
Latching
Option
Latching
Supervisory switches can be latching or non-latching.
Non Latching
Latching
Detectors programmed as Supervisory can be latching or non-latching.
Non Latching
Latching
Wireless photoelectric detectors
Non Latching
Wireless heat detector
Latching
Wireless photoelectric detectors
Non Latching
Use this switch type for manual pull stations. This input is always latched. The switch can
clear only when an alarm is reset.
Latching
Use this switch type for monitoring water flow in a Sprinkler System. Switch closure will
Non Latching
cause a sprinkler alarm. Water flow switches can be programmed as latching or non-
latching.
You can program a delay of up to 90 seconds to be used with a water flow switch. The
delay allows for normal, brief changes in Sprinkler System water pressure. The water flow
alarm will not activate unless the switch is active for the programmed delay time.
Note: Waterflow delay of the FACP and the waterflow device shall not exceed 90 seconds.
If a delay is used, the system begins counting down when the switch closes. If the switch
opens (restores) before the timer expires, a water flow alarm is not generated. If the water
flow switch remains closed after the timer expires, a water flow alarm will be generated.
Latching
Use this switch type for tamper monitoring of sprinklers and other fire protection devices. If
Non Latching
a contact closes, a sprinkler supervisory event will be generated. Supervisory switches can
be latching or non-latching.
System-level, non latching switch. This switch is an alternative way of causing a fire drill. It
has the same operation as the fire drill option available from the annunciator. When the
switch is activated, a fire drill begins; when the switch is de-activated, a fire drill ends.
System-level switch provides an alternate way to silence the system; same effect as
pressing the Silence key.
System-level switch provides an alternate way to reset the system; same effect as pressing
the Reset key.
Positive acknowledge switch. This switch must be used in zones programmed as Positive
Alarm Sequence (see Table 8.2).
If an acknowledge switch closes when an alarm or trouble condition is not already in
progress, a trouble will occur.
You must use a UL listed normally open, momentary switch type. The switch must be rated
at 5V, 100 mA (minimum) and be used with an EOL resistor for supervision.
Table 8.3 Point Programming for Internal SLC Module (Continued)
Comments
6700 Manual — P/N LS10148-001SK-E:F 8/29/2022
Point

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents