This section of the manual describes how to manually program the control panel from the built-in annunciator. Each subsection describes
these menu options. All options described in this section can be performed using the HFSS Honeywell Fire Software Suite.
NOTE: JumpStart auto-programming should be run Before any customized programming is performed. Thoroughly test the system after
running JumpStart because it automatically programs the system, searching for and configuring all SLC and SBUS devices it finds. JumpStart
allows you to confirm the integrity of the installation prior to performing any custom programming. After determining that the hardware is properly
installed, custom programming can be performed.

8.1 UL 864 Programming Requirements

NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES:
This product incorporates field programmable software. In order for the product to comply with the requirements in the Standard for Control
Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values or not used
Programming Option
Time Options
Time Options
Communication Options
Silencing Options
Display Oldest Event
1
Alarm Verification
2
Manual Release Switch
1
When the 2-count delay is active, you cannot use the Alarm Verification.
2
The Manual Release Switch shall override any pre-discharge delays resulting in an immediate release or start of the Manual Release Delay period.
The delay period shall be 30 seconds or less from the activation of the switch to the actuation of the releasing device(s).
NOTE: Use software version 7.0 or higher.

8.2 Modules

This section lists the options available under the Module Option in the Program Menu. The types of modules available for the control panel
are the 6855, 5860, or 6860 LCD Annunciator, 5824 Serial/Parallel input/output, 5880 LED Input/Output module, 5496 NAC Expander,
5895XL Power supply, SK-NIC Network Interface Card, and 5865 LED Annunciator.
8.2.1 Edit Modules
The features you can edit when this option is selected are Module Name and Class of Wiring (Class A or Class B). To edit an existing mod-
ule, follow these steps:
1.
Login to the panel.
2.
Select 7 to access the Program Menu.
3.
Press 1 to access the Module Menu.
4.
Press 1 to edit a module.
5.
Use the up or down arrow to select the module you want to edit.
Editing Module ID
6.
Press the up or down arrow key to modify the Module ID.
NOTE: You cannot edit the module ID for any internal devices or the SK-NIC.
Naming Modules
You can assign an English name to a hardware module to easily identify it on a display.
7.
To edit a module name, press the up or down arrow to select each character for the modules name (or press the right arrow to bypass the
name edit). Press the right arrow to move to the next character.
NOTE: See Appendix A for instructions on how to edit the names.
74

Section 8: Programming

Menu Item
Auto-Resound
Yes
Low AC Report Delay
Yes
Auto Test Time
Yes
Auto Silence
Yes
Y (Enabled)
Yes
N (Disabled)
No
Alarm Verification
Yes
Manual Release
Yes
Table 8.1 Programming Requirements
at all as indicated below.
Permitted in
Possible Settings
UL 864 (Y/N)
4 or 24 hours
0-30 hours
4, 6, 12, and 24 hrs
0-60 minutes
Yes or No
Yes or No
60-250 seconds
(confirmation period)
0-120 Seconds
(delay period)
6700 Manual — P/N LS10148-001SK-E:F 8/29/2022
Settings Permitted in UL 864
4 hours if you use SWIFT devices.
24 hours if you use other devices
1-3 hours
4 or 6 hours
3-60 minutes
Yes
No
0-60 seconds
0-30 Seconds
(delay period)