5880 LED Driver Module
4.11.2 FACP Connection
The 5880 connects to the panel via the SBUS. Make connections as shown below. After the 5880 is connected to the panel, it must be added
to the system. Programming is described in Section 8.
TROUBLE
NO
C
NC
supervised,
power-limited,
4.11.3 LED Wiring
There are four 12-pin connectors on the 5880 board for connecting LEDs. Each LED gets its power from Pin 11. Internal resistors are sized
so that there is approximately 10 mA of current for each LED; no series resistors are required. LED outputs can be mapped to output circuits.
See Section 8 for Programming details.
Wire the LEDs as shown in Figure 4.32.
On connector P1, Pin 12 is a programmable Open Collector Output for controlling a piezo. If used, the 5880 piezo will match the piezo pat-
tern of the onboard or remote annunciator.
NOTE: The circuit connected to "Open Collector Output" (last pin on P1) must be current-limited so that no more than 100 mA of current is
allowed to flow into the Open Collector Transistor.
6700 Manual — P/N LS10148-001SK-E:F 8/29/2022