To help calculate the size of the PV array configuration use the
configurations:
PV array example 24V battery with 150V solar charger:
• Minimum number of cells in series: 72 (2x 12V panel in series or 1x 24V panel).
• Recommended number of cells for highest controller efficiency: 144 cells (4x 12V panel or 2x 24V panel in series).
• Maximum: 216 cells (6x 12V or 3x 24V panel in series)
PV array example 48V battery with 150V solar charger:
• Minimum number of cells in series: 144 (4x 12V panel or 2x 24V panel in series).
• Maximum: 216 cells (6x 12V or 3x 24V panel in series).
• Provide a means to disconnect all current-carrying conductors of a photo-voltaic power source from all other
conductors in a building or other structure.
• Be aware that at low temperatures and depending on local conditions and cell specifications the open
circuit voltage of a solar array may exceed the array's rated maximum open circuit voltage. In that case the
number of cells in series must be reduced.
• A switch, circuit breaker, or other device, either AC or DC, shall not be installed in a grounded conductor if
operation of that switch, circuit breaker, or other device leaves the grounded conductor in an un-grounded
state while the system remains energized.
• Do not use solar panels with optimizers. In worst case, the use of optimizers will cause irreparable damage
to the solar charger.
• Use flexible multi stranded copper cable for the screw connections . See chapter
precautions
[1].
• For MC4 models: several of the solar charger's MC4 pairs may be needed to parallel solar panel strings. Be
aware that the maximum current through a MC4 connection cannot exceed 30A.

4.4. Grounding

Battery grounding
The solar charger can be installed in a positive or in a negative grounded system.
Apply a single ground connection, preferably close to the battery, to prevent system issues or ground loops.
Chassis grounding
A separate ground path for the chassis ground is permitted because the chassis is isolated from the positive and the negative
terminals.
PV array grounding
Page 10
MPPT solar charger manual
120 W
120 W
12 V
12 V
240 W
12 V
20 A
Examples of series, parallel and series/parallel solar arrays.
MPPT sizing
120 W
120 W
120 W
12 V
12 V
12 V
480 W
24 V
20 A
calculator. Alternatively, use one of these PV array
Wiring safety
120 W
12 V
Installation

Advertisement

Table of Contents
loading

This manual is also suitable for:

Smartsolar mppt 150/35Scc115045212

Table of Contents