Grounding; Connection Overview - Victron energy SmartSolar MPPT 150/60 Manual

Solar charger
Hide thumbs Also See for SmartSolar MPPT 150/60:
Table of Contents

Advertisement

4.4. Grounding

Battery grounding
The solar charger can be installed in a positive or in a negative grounded system.
Apply a single ground connection, preferably close to the battery, to prevent system issues or ground loops.
PV array grounding
The positive and negative of the PV array should not be grounded.
Ground the frame of the PV panels to reduce the impact of lightning.
Do not connect the solar charger to a grounded PV array. Only one ground connection is allowed, and this should be near the
battery.
Ground fault detection
The solar charger does not have internal ground fault protection.
The USA National Electrical Code (NEC) requires the use of an external ground fault protection device (GFPD).
The system electrical negative should be bonded through a GFPD to earth ground at one (and only one) location.
When a ground fault is indicated, battery terminals and connected circuits may be un-grounded and
hazardous.

4.5. Connection overview

ID
Description
A
Ground screw.
B
Rotary switch.
C
LEDs.
D
VE.Direct socket.
E
Battery screw terminals.
F
PV screw terminals.
G
Relay screw terminals.
H
Remote on/off terminals.
Page 13
MPPT solar charger manual
TR Model.
MC4 model.
Installation

Advertisement

Table of Contents
loading

Table of Contents