Test Connections to the Field Wiring Compartment

During calibration set up the transmitter as shown in figure 8. Except for 4211 and 4221 transmitters, the field circuit
printed wiring board is used. A 4211 or 4221 transmitter uses a barrier strip (key 11, figure 4) mounted in the field
wiring compartment for field wiring connections. For calibration and bench check of the 4211 or 4221 transmitter,
make connections to the barrier strip (key 11).
For a 4210, 4215, or 4220 transmitter with position switches, the transmitter can be calibrated with or without the
position switch outputs being connected.
Note
On units with position switches, the (R) terminal on TB3 must be connected to the power supply negative (-) terminal for proper
instrument operation, even if the position switch outputs are not used.
For a 4211 or 4221 transmitter without position switches, use a two wire system with the indicating device installed as
shown in figure 8.
Figure 8. Calibration and Bench Check Test Setup
TRANSMITTER COMPARTMENT
NOTES:
 1  CONNECT DVM TO TEST POINTS AS DIRECTED BY CALIBRATION AND MAINTENANCE PROCEDURES.
 2  INSURE THAT THE CONNECTOR ATTACHED TO J1 (VIEW A) IS NOT REVERSED WHEN INSTALLING IT
ON THE PRINTED WIRING BOARD.
 3  THE INDICATING DEVICE CAN BE A VOLTMETER ACROSS A 250 OHM RESISTOR OR A CURRENT METER.
 4  SEPARATE RETURN LEAD REQUIRED FOR RELAYS. RETURN WIRE MUST BE CONNECTED EVEN IF RELAY OUTPUTS ARE NOT USED.
B1948‐5
TO RFI
FILTERS
J1 FROM
J3
RFI FILTERS
FIELD WIRING
COMPARTMENT
4200 Transmitters
September 2022
J1
VIEW A
(SEE VIEW A)
+ 24 VOLT
DC POWER
SUPPLY
19