Bosch FPC-500 Installation Manual page 9

Conventional fire panel
Hide thumbs Also See for FPC-500:
Table of Contents

Advertisement

Conventional fire panel
Z1 ... Z8
IN
ALARM RLY
FAULT RLY
OC
AUX 24 VDC
Features
Bosch Sicherheitssysteme GmbH
Conventional zones 1 to 8
(max. 2 on FPC-500-2, max. 4 on FPC-500-4)
Inputs (max. 1 on FPC‑500‑2 and FPC‑500‑4,
max. 2 on FPC‑500‑8)
Alarm relay
Fault relay
Transistor output for extension cards
(0 on FPC‑500‑2, 4 on FPC‑500‑4, 8 on
FPC‑500‑8)
AUX power supply
Alarm verification: The user is prompted to verify the alarm.
Intermediate alarm storage: an alarm triggered by an
automatic detector is reset automatically after 20 seconds
(adjustable) by the panel. If there is an additional alarm
within 10 minutes in this zone, the notification appliances
are enabled. Otherwise the pre-alarm is reset automatically.
Dual-zone dependency on neighboring zones.
Dual-detector dependency for detectors in a zone.
Alarm counter for 999 alarms.
Event memory for 1000 entries.
Three operating levels, two of them protected with freely
selected code.
Up to 8 monitored detector zones depending on panel
version.
Up to 2 monitored inputs available depending on panel
version.
One alarm and one fault relay.
Up to 8 additional transistor or relay outputs, freely
programmable, depending on panel version.
System Overview | en
2020.02 | 9.0 | F.01U.172.980
9