Information As Per En 54-4, Chapter - Bosch FPC-500 Installation Manual

Conventional fire panel
Hide thumbs Also See for FPC-500:
Table of Contents

Advertisement

56
en | Technical Data
6.4
Information as per EN 54‑4, chapter 7.1
a) This is a power supply unit that is installed in the FPC‑500
Fire Panel. It provides power to the device and the connected
peripherals and is used to charge the two connectable batteries.
b) Technical data
1) Recommended power
output
2) Power supply
Operating voltage
3) Communication
parameters
4) Fuse values
5) Batteries
6) Max. current
consumption
7) Max. battery inner
resistance
8) I
I
max, a
I
max, b
9) Cable parameters
Battery
Board power supply
230-V power supply
2020.02 | 9.0 | F.01U.172.980
min
Conventional fire panel
61 W
230 VAC +10%/-15%, 50–60 Hz
26 VDC to 29 VDC
None
3.15 A/250 V
2 x 7.0–7.2 Ah (max.) lead gel
battery
2.3 A
800 mOhm
70 mA
0.7 A
2.3 A
Cable enclosed
Wired ex works
1.5-mm
2
standard cable
Bosch Sicherheitssysteme GmbH

Advertisement