Conventional fire panel
Notice!
Note that the maximum line resistance for the relay outputs is
22.5 Ohm.
3.3.6

Extensions

The extension modules offer four connections activated by
transistors or relay.
Notice!
The relay outputs can switch a maximum of 1 A @ 30 VDC each.
The transistor outputs switch a maximum of 20 mA @ 24 VDC
each. Inductive loads are not permitted.
3.4

Initial Start-Up

As soon as the fire panel is connected to the power for the first
time, an LED and buzzer test begins. This is completed the first
time a key is pressed.
In the initial start-up, you must make the following basic
settings:
3.4.1

Setting the Language

To set the language, proceed as follows:
i
ACK
3.4.2

Setting the Time and Date

Set the current time and date. The current time and date are
important for functions such as
Bosch Sicherheitssysteme GmbH
Set the language
Set the time and date
Use the arrow keys to set the desired language.
Confirm your selection in the menu with the ACK
key.
Event memory and
Installation | en
2020.02 | 9.0 | F.01U.172.980
25