Resetting Zones - Bosch FPC-500 Installation Manual

Conventional fire panel
Hide thumbs Also See for FPC-500:
Table of Contents

Advertisement

Conventional fire panel
4.1.4

Resetting Zones

In this menu, you can specify the delay times for resetting
zones. You can specify how long the zones can be disconnected
from the power and how long the stabilization time of the
detector should last. This setting is used for the zone test,
restarting the fire panel and intermediate alarm storage.
Cut For
1
4
1
1
Stabilize for
1
4
2
1
Bosch Sicherheitssysteme GmbH
Press zone key 1. This takes you to the System
Config menu.
Press zone key 4.
This takes you to the Zone Reset submenu.
Press zone key 1.
This takes you to the Cut For submenu.
Press zone keys 1 to 5.
5
...
1 1s
2=5s (default setting)
3 10s
4 15s
5 20s
Press zone key 1. This takes you to the System
Config menu.
Press zone key 4.
This takes you to the Zone Reset submenu.
Press zone key 2.
This takes you to the Stabilize For submenu.
Press zone keys 1 to 5.
5
...
1 1s
System Configuration | en
2020.02 | 9.0 | F.01U.172.980
31