46
en | System Configuration
4.5.2
Alarm Relay
In the Alarm Relay submenu, you can specify the properties of
the alarm relay. These include the Silencable and Drillable
settings. You can use Silencable to specify whether the relay
can be silenced manually. Drillable specifies whether the alarm
relay is also activated during a manual alarm (Drill/Evac).
Alarm relay can be muted
5
2
1
1
Alarm relay follows manual alarm
5
2
2
1
2020.02 | 9.0 | F.01U.172.980
Press zone key 5.
This takes you to the Output Config menu.
Press zone key 2.
This takes you to the Alarm Relay submenu.
Press zone key 1.
This takes you to the Silencable submenu.
Press zone keys 1 or 2.
2
...
1 Silencable
2=Not Silencable (default setting)
Press zone key 5.
This takes you to the Output Config menu.
Press zone key 2.
This takes you to the Alarm Relay submenu.
Press zone key 2.
This takes you to the Drillable submenu.
Press zone keys 1 or 2.
2
...
1 Drillable
2= Not Drillable (default setting)
Conventional fire panel