52
en | Technical Data
Updating the panel software (firmware) via USB
You can update the panel software using the USB port on the
lower left side of the main board. To do this, connect the USB
port to your computer and install the programming software
supplied on the CD. Follow the on-screen instructions.
6
Technical Data
Zones
Max. number of detectors in
accordance with EN 54‑2
Max. number of detectors per
zone in accordance with
EN 54‑2
Max. number of extensions
Prog. inputs
AUX output
Alarm device output
Relay
6.1
Electrical Data
Power supply voltage
Current consumption
AC power consumption
Operating voltage
2020.02 | 9.0 | F.01U.172.980
Conventional fire panel
FPC-500‑
FPC-500‑
2
4
2
4
64
128
32
0
1
1
1
2
2
FPC-500‑
FPC-500‑
2
4
230 VAC +10%/-15%, 50–
60 Hz
275 mA
312 mA
80 W
21.4 VDC to 29 VDC
Bosch Sicherheitssysteme GmbH
FPC-500-
8
8
256
2
2
FPC-500-
8
375 mA