Product Designation; Technical Specifications - Bosch FMC-300RW-GSRRD Installation Manual

Hide thumbs Also See for FMC-300RW-GSRRD:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 12
12
en

Product designation

Manual conventional detector for use in interior areas, surface-mounted,
resettable:
- FMC-300RW-GSRRD manual call point, red /
- FMC-300RW-GSRBU manual call point, blue
- FMC-300RW-GSRYE manual call point, yellow.
Installation
For installation, see Fig. 1- Fig. 8, page 4, 6.
Connection (see Fig. 3, page 4)
Position
Description
1
b1, a1 / b2, a2 Incoming/outgoing
2
E
3
-----------------
Functional test
Press the pane in; see Fig. 9.1.
If an alarm is triggered, the LED is illuminated and the color display in
the window changes from white to red.
To reset the manual call point to its starting position:
1.
Unlock the maintenance flap with the test key and pull it forward; see
Fig. 9.2 and 9.3.
2.
Insert the test key into the top opening and push it down; see Fig. 9.4.
The LED goes out and the color display in the window changes from red
to white.
3.
Return the maintenance flap to its starting position.

Technical specifications

Operating voltage
Current consumption
Alarm resistor
Permissible operating
temperature
Protection class as per EN
60529
Dimensions
F01U045275 A5 | 2008.03
Function
Shielding
End of line resistor (EOL)
20 V DC (8.5 V DC . . 30 V DC)
specified by the respective security system
820 Ohm (+/- 10%, 8.5 to 30 VDC)
-25 °C . . +70 °C
IP 54
87 x 87 x 56 mm
Bosch Sicherheitssysteme GmbH