GFK-2573AB
Programmer Limits
Number of I/O-Controllers
Number of I/O-Devices
Total number of devices
Hot-swappable
For product standards, general operating specifications, and installation requirements, refer to PACSystems RX3i System
Manual, GFK-2314.

EMC Installation Requirements

To meet EN 55011 and FCC Class A radiated emissions, the Control system in which the IC695PNC001 module is used
shall be mounted in a metal enclosure when three or more IC695PNC001 modules are used. All surfaces of the
enclosure must be adequately grounded to adjacent surfaces to provide electrical conductivity. Wiring external to the
enclosure must be routed in a metal conduit or the equivalent. The conduit must be mounted to the enclosure using
standard procedures and hardware to ensure electrical conductivity between the enclosure and conduit.
When installing, operating, or maintaining the IC695PNC001, personnel must ensure any electrostatic charge is
discharged through the use of a grounded ESD strap or other means.

Installation Location

This product is intended for use with the RX3i system. Its components are considered open equipment (having live
electrical parts that may be accessible to users) and must be installed in an ultimate enclosure that is manufactured to
provide safety. At a minimum, the enclosure shall provide a degree of protection against solid objects as small as
12mm (fingers, for example). This equates to a NEMA/UL Type 1 enclosure or an IEC60529 IP20 rating providing at
least a pollution degree 2 environment. For details about installing RX3i rack systems, refer to PACSystems RX3i System
Manual, GFK-2314.

Installation in Hazardous Areas

The following information is for products bearing the UL marking for Hazardous Areas or ATEX marking for explosive
atmospheres:
CLASS 1 DIVISION 2 GROUPS ABCD
This equipment is an open-type device and is meant to be installed in an enclosure suitable for the environment
that is only accessible with the use of a tool.
Suitable for use in Class I, Division 2, Groups A, B, C, and D Hazardous Locations, or non-hazardous locations only.
WARNING
EXPLOSION HAZARD - SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2.
WHEN IN HAZARDOUS LOCATIONS, TURN OFF POWER BEFORE REPLACING OR WIRING MODULES.
128 (32 RX3i CPU targets × 4 IO-Controllers per RX3i CPU)
4080 (255 per network × 16 PROFINET networks)
4208 (does not include backplanes, power supplies, or I/O modules)
Yes
Jul 2022
3