Emerson PNC001-A Series Important Product Information page 15

Pacsystems rx3i profinet controller
Table of Contents

Advertisement

GFK-2573AB
Subject
RX3i PROFINET
Scanner Version
Requirements
Programmer version
requirements
4
Attempts to store a configuration utilizing this feature to a prior-release PNC001 will result in an Unable to deliver configuration to module fault, which
leaves the PNC001 in an un-configured state.
Feature
If using PROFINET System
Redundancy, users MUST
upgrade the PNC001
(PROFINET Controller) to
Version 2.2 or later
firmware.
IC695CMM002/004
support in IC695PNS001-
Bxxx, IC695PNS001, and
IC695CEP001
RX3i PNC001 Release 3.00
New HW/FW to address
component obsolescence
RX3i PNC001 Release 2.26
Support Remote Get
Device Information
COMMREQ
IC695CMM002/004
support in IC695PNS001-
Bxxx, IC695PNS001, and
IC695CEP001
RX3i PNC001 Release 3.00
RX3i PNC001 Release
2.11(or later)
• 128 PROFINET Device
Support
4
• Critical Network Port
Minimum Version Required
Effective with PME 8.6 SIM 3 and PME 8.5 SIM 11 (PPS 2.6
SIM3 and PPS 2.5 SIM11), the PNC001 is configured to use
RT Class 2 for redundant PROFINET connections. To meet
specifications, this requires PNC001 firmware 2.2 or later.
Under these conditions, redundant VersaMax and/or CEP
PROFINET I/O will NOT connect or transfer I/O or Alarm
Data if the PNC001 is running firmware prior to Version
2.2.
IC695PNS001 Bxxx or IC695PNS101 with firmware version
3.35 or later and GSDML version: GSDML V2.3
IntelligentPlatformsLLC RX3iPNS-20210817.xml
IC695PNS001 with firmware version 3.00 or later and
GSDML version: GSDML-V2.3-GEIP-RX3iPNS-
20170109.xml.
IC695PNS001 with firmware version 2.41 or later and
GSDML version: GSDML-V2.3-GEIP-RX3iPNS-
20160602.xml.
PME 10.00 or later
PME 8.50 SIM 9 or 8.60 SIM 1
PME 8.50 SIM 9 or 8.60 SIM 1
4
Jul 2022
13

Hide quick links:

Advertisement

Table of Contents
loading