Electrical connection

2.
The Varivent® couplings enable flush-mount installation.
4.1.4
Inlet and outlet runs
NOTICE
The thermal measuring principle is sensitive to disturbed flow conditions.
Install the measuring device as far away as possible from any flow disturbances. For further
information → ISO 14511.
Install the sensor upstream from fittings such as valves, T-pieces, elbows etc.
To attain the specified level of accuracy of the measuring device, the inlet and outlet runs
mentioned below must be maintained at the very minimum.
If several flow disturbances are present, maintain the longest specified inlet run.
1
5 × DN
4
15 × DN
 6
Inlet and outlet runs
1
Reduction
2
Expansion
3
90° elbow or T-piece
4
Pump
5
Control valve
6
2x 90° elbow, 2- or 3-dimensional
5
Electrical connection
5.1

Connection conditions

5.1.1
DC voltage version with M12x1 connector
DTT35: According to the 3-A Standards electrical connecting cables must be smooth,
corrosion-resistant and easy to clean.
12
2
3 × DN
5
3 × DN
5 × DN
3 × DN
10 × DN
3 × DN
Flowphant T DTT31, DTT35
3
5 × DN
3 × DN
6
5 × DN
3 × DN