Endress+Hauser Flowphant T DTT31 Flowphant T DTT35 Operating Instructions Manual page 24

Flow switch
Table of Contents

Advertisement

Operation options
Function group
Function
SPL
SP2L
RSP
RSP2
TSP
TSP2
TRSP
TRSP2
6.2.9
Settings for output - 1 x analog output (4 to 20 mA) and 1 x switch output
Function group
Function
4-20
MODE
Output 1
FCUR
OUT
MODE
Output 2
UNIT
24
Settings
Switch point
RUN
"Learn"
WAIT
Switchback point
0.0
value
Switch point
0.0
delay
Switchback point
0.0
delay
Settings
Measured
FLOW
variable for
TEMP
analog output
Failure current
MIN
MAX
HOLD
Switching mode
FLOW
TEMP
Technical unit
xC
xF
Flowphant T DTT31, DTT35
Description
RUN, WAIT: Take the current flow rate as the
switch point SP or SP2.→  12,  18
Enter value 0 to 95 % in increments of 1 %.
Factory setting: 40 %
Value must be at least 5 % smaller than
the switch point (SP or SP2).
Or optionally for RSP2:
Enter value –20 to +80 °C (–4 to +176 °F) in
increments of 1 °C (1 °F) if the switching mode
MODE is set to temperature TEMP.
Value must be at least 5 °C (9 °F)
smaller than switch point 2 (SP2).
Factory setting: 50 °C
Can be set anywhere between
0 to 99 s in increments of 1 s.
Factory setting: 0 s
Can be set anywhere between
0 to 99 s in increments of 1 s.
Factory setting: 0 s
Description
Output FLOW: flow rate or TEMP:
temperature
If TEMP is set, the measuring range is
fixed at –20 to +85 °C (–4 to +185 °F) .
Factory setting: FLOW
Current value in the event of an error:
MIN = ≤ 3.5 mA
MAX = ≥ 21.7 mA
HOLD = last current value
Factory setting: MAX
Output switching mode FLOW: flow rate or
TEMP: temperature
Factory setting: temperature (TEMP)
Temperature unit selection (°C or °F)
Function is only visible if the switching
mode MODE is set to temperature
TEMP in the 2nd output.
Factory setting: °C
Endress+Hauser