Endress+Hauser Flowphant T DTT31 Flowphant T DTT35 Operating Instructions Manual page 22

Flow switch
Table of Contents

Advertisement

Operation options
6.2.6
Basic settings
Function group
Function
BASE
DISP
Basic settings
UNIT
TAU
DESI
6.2.7
Calibration
Function group
Function
CAL
HIF
Calibration
LOWF
22
Settings
Display
PV
PVRO
TMP
TMPR
OFF
OFFR
Technical unit
xC
xF
Damping
0.0
DESINA
NO
Only for 2 x PNP
YES
switch outputs
Settings
Learn High Flow
RUN
WAIT
Learn Low Flow
RUN
WAIT
Flowphant T DTT31, DTT35
Description
Displays the current measured value
Displays the current measured value rotated
by 180 °
Displays the current medium temperature
Displays the current medium temperature
rotated by 180 °
Display off
Display off, rotated by 180 °
Factory setting: current measured value (PV)
Medium temperature displayed in the unit °C
or °F
Only visible if the current medium
temperature TMP is selected in the
DISP mode.
Factory setting: °C
Measured value damping with regard to
display value and output:
0 (no damping) or 9 to 40 s (in increments of
1 s)
Factory setting: 0 s
Behavior as per DESINA:
The PIN assignment of the M12 connector is
in accordance with the DESINA Guidelines
(DESINA = distributed and standardized
installation technology for machine tools and
manufacturing systems)
Factory setting: NO
Description
Setting for the maximum flow rate that
occurs. 100 % value →  11,  17
Setting for the maximum flow rate that
occurs. 0 % value →  11,  17