Endress+Hauser Flowphant T DTT31 Flowphant T DTT35 Operating Instructions Manual page 10

Flow switch
Table of Contents

Advertisement

Installation
• The sensor tip must be completely surrounded by the
medium
• Position the sensor tip in the area of maximum flow
velocity (pipe center)
• Minimum sensor immersion length
L
≥ 10 mm (0.4 in).
i
Orientation
• For horizontal pipes: lateral installation. Installation
from above only if the pipe is completely filled with
medium
• For vertical pipes: installation in the ascending pipe
• For DTT35: install at an angle of at least 3 ° for self-
draining
NOTICE
If the device is installed incorrectly this can result in
incorrect measurements!
Do not install in down pipes open towards the end.
The sensor tip should never touch the pipe wall.
10
v
m
 2
Installation instructions (example)
= 3°
 3
Correct orientation
 4
Incorrect installation!
Flowphant T DTT31, DTT35
%