Huawei SmartLi 2.0 User Manual page 18

Hide thumbs Also See for SmartLi 2.0:
Table of Contents

Advertisement

SmartLi 2.0
User Manual
Leakage Handling
Electrolyte overflow may damage the equipment. It will corrode metal parts and
boards, and ultimately damage the boards.
Electrolyte is corrosive and can cause irritation and chemical burns. Should you
come into direct contact with the battery electrolyte, do as follows:
Battery Room Fire Safety
The fire safety of the battery room must comply with local laws and regulations
as well as applicable standards such as NFPA 855, NEN-1010, or GB 50016, and
meet the following requirements:
Issue 13 (2023-03-26)
NO TICE
Inhalation: Evacuate from contaminated areas, get fresh air immediately, and
seek immediate medical attention.
Eye contact: Immediately wash your eyes with water for at least 15 minutes,
do not rub your eyes, and seek immediate medical attention.
Skin contact: Wash the affected areas immediately with soap and water and
seek immediate medical attention.
Intake: Seek immediate medical attention.
An independent battery room should be deployed, and its wall should comply
with 2-hour fire resistance rating. A maximum of eight lithium battery
cabinets can be deployed in a battery room.
The battery room must not be located in environments where explosive gases
may exist or be released.
The battery room must not be located near or below areas with water
leakage risks, such as water reservoirs, water landscapes, and water towers.
The indoor layout of batteries should comply with local fire protection laws
and regulations in aspects such as production scenarios and the safe distance
and layout of buildings and materials.
Do not store combustible materials in the battery room. Keep such materials
at least 3 m away from the battery room.
A battery room deployed outdoors should be at least 3.0 m away from the
following places: restricted areas, combustible warehouses, dangerous goods,
high-stacking warehouses, power infrastructure, public roads, and buildings.
The battery room must be isolated from the adjacent area by fire
compartmentation. Holes should be sealed by firestop material. The fire
resistance and thermal insulation capabilities should be the same as that of
the partition wall.
The battery room should be equipped with fire extinguishers filled with
halogenatedane, heptafluoropropane, perfluorohexanone, carbon dioxide, or
dry powder. Each fire protection unit must be equipped with at least two fire
extinguishers, which should be checked and replaced periodically.
The battery room should be equipped with cabinet-level or room-level CO
sensors, smoke sensors, and temperature sensors. It is recommended that H
Copyright © Huawei Digital Power Technologies Co., Ltd.