Figure 5-53 Installing a communications cable between the SmartLi and the UPS
(UPS5000-S-1600 kVA)
(1) Intelligent detection board
2
(4) Master SmartLi cabinet 1
Installing a Communications Cable Between the Master Lithium Battery
Cabinet and the Upper-Layer Management System
Issue 13 (2023-03-26)
If you need to log in to the WebUI of the SmartLi, connect the network port
on a PC to the FE port on the monitoring interface unit of the SmartLi.
If the SmartLi needs to connect to the NetEco, connect the NetEco to the FE
port on the monitoring interface unit of the SmartLi over a LAN switch.
If the SmartLi needs to connect to the ECC800-Pro, connect the ECC800-Pro to
the FE port on the monitoring interface unit of the SmartLi through the PoE
port of a smart ETH gateway.
If the SmartLi needs to connect to a third-party network management device:
If the communications protocol is Modbus-RTU, connect the third-party
network management device to the RS485 port on the monitoring
interface unit of the SmartLi.
If the communications protocol is Modbus-TCP, connect the third-party
network management device to the FE port on the monitoring interface
unit of the SmartLi.
Copyright © Huawei Digital Power Technologies Co., Ltd.
(2) Intelligent detection board
1
(5) Master SmartLi cabinet 2
5 Installation and Cable Connection
(3) Two-in-one adapter
(6) Master SmartLi cabinet 3
93