Procedures For Transfer Between Operation Modes; Transfer From Normal Mode To Battery Mode; Transfer From Normal Mode To Bypass Mode; Transfer From Bypass Mode To Normal Mode - Vertiv Liebert EXM2 User Manual

100kva to 250kva ups
Hide thumbs Also See for Liebert EXM2:
Table of Contents

Advertisement

Vertiv™ Liebert® EXM2 UPS User Manual
N O .
D escription
1
Battery cold start button

6.3 Procedures for Transfer between Operation Modes

6.3.1 Transfer from Normal Mode to Battery Mode

Open the external power switch to isolate the mains power and initiate the UPS on battery mode. To transfer the UPS back to
normal mode, close the external power switch to reconnect the mains power to the UPS. 10 seconds later, the rectifier restarts
automatically, and the UPS works in normal mode.

6.3.2 Transfer from Normal Mode to Bypass Mode

Click the Inverter Off key shown in Figure 6.8 below, and the UPS will transfer to bypass mode.
Figure 6.8 Transfer U PS to Bypass m ode
N O TE: In bypass m ode, the load is directly fed by the m ains pow er instead of the pure A C pow er
from the inverter.

6.3.3 Transfer from Bypass Mode to Normal Mode

When the UPS is in bypass mode, click the Inverter On key in Figure 6.9 on the next page, and the inverter starts up. Then the
UPS is transferred from bypass mode to normal mode.
6 Single UPS Operation Introduction
111