Version: V1.4 Revision date: Septem ber 1, 2020 BO M : 31013755 Vertiv provides custom ers w ith technical support. Users m ay contact the nearest Vertiv local sales office or service center. 2018, Copyright 2020 by Vertiv Tech Co., Ltd.
Page 4
N ear heat sources or strong electrom agnetic interferences D isclaim er Vertiv disclaim s any and all responsibility or liability for the defects or m alfunction caused by: Application range or operating environm ent outside the specif ications ...
Page 5
C o n fo rm ity a n d sta n d a rd s 1. The U PS com plies w ith 2014/35/EU (LVD ), 2014/30/EU (EM C), 2011/65/EU (Rohs) and the follow ing product standards for U PS: ...
Page 6
The Manual Describes Following Equipment P ro d u c t M o d e l 30kVA EXS 0030kTH 16FN 01000 40kVA EXS 0040kTH 16FN 01000...
Contents Chapter 1 Overview ....................................1 1.1 Features ....................................1 1.2 D esign C oncept ..................................1 1.2.1 System D esign ................................1 1.2.2 Bypass ..................................2 1.2.3 System C ontrol Principle ............................3 1.2.4 U PS Pow er Supply Sw itch C onfiguration ......................4 1.2.5 Battery Circuit Breaker (BC B) ..........................5 1.3 Parallel System ...
Page 8
5.3.1 Transfer From N orm al M ode To Battery M ode ....................50 5.3.2 Transfer From N orm al M ode To Bypass M ode ....................51 5.3.3 Transfer From Bypass M ode To N orm al M ode ....................52 5.3.4 Transfer From N orm al M ode To M aintenance Bypass M ode ................53 5.3.5 Transfer From M aintenance Bypass M ode To N orm al M ode ...
Page 9
10.2 Environm ental C haracteristics ............................93 10.3 M echanical C haracteristics ............................94 10.4 Electrical C haracteristics (Input Rectifier) ........................94 10.5 Electrical C haracteristics (Battery) ..........................94 10.6 Electrical C haracteristics (Inverter O utput) .......................95 10.7 Electrical C haracteristics (Bypass Input) ........................95 Appendix 1 LCD Parameters Setting ..............................96 Appendix 2 Glossary ...................................100 Appendix 3 Hazardous Substances And Content ..........................101...
Chapter 1 Overview D eveloped by Vertiv, the Liebert EXS 30kVA and 40kVA U PS (UPS for short) is an intelligent online U PS system with sine wave output, and offers reliable and high-quality AC pow er to the precision instrum ent.
(P a ra lle l Sy ste m ) In the event of a fault in a U PS m odule, it will autom atically exit from the parallel system . If the system is still capable of providing the required load, the rem aining m odules will continue to supply the Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
2. Parallel cables are connected in a ring, providing both system reliability and redundancy. 3. The total load of the parallel system can be queried from the LCD of each U PS. Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
Page 13
This m eans that the battery pow er can be used independently to im prove the system availability, to a certain extent. Figure 1-4 Schem atic diagram of battery m ode Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
Page 14
Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
To protect against the battery overcharge dam age caused by long tim e boost charge, a protect tim e setting is essential. The lim it of tim e setting shall be configured by service engineer through the Vertiv setting software.
1. The U PS should be installed by a qualified engineer in accordance w ith the inform ation provided in this section. In the event of any problem s, contact your local Vertiv service center im m ediately. 2. The U PS m ust N O T be sw itched on w ithout the approval of the com m issioning engineer.
1. U se a cutting plier to cut off the packing belt, and rem ove the honeycom b board, as show n in Figure 2-2. Figure 2-2 Rem oving packing belt and honeycom b board Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
If necessary, install indoor extractor fans to aid cooling-air flow to avoid room tem perature buildup. Air filters should be used w hen the U PS is to operate in a dirty environm ent. Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
Besides the local regulations, to enable routine tightening of the power term inals within the U PS, it is recom m ended that clearance around the front of the UPS should m aintain a clearance at least 1200m m . Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
Page 20
The pow er cable m ust be selected according to the current and voltage values in Table 3-1 as w ell as the local w iring regulations, and take environm ental conditions (tem perature and physical m edia) into consideration, then refer to Table 3B in IEC 60950-1. Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
Page 21
3. W hen routing the cables inside the cabinets, it is required to bind and fix the cables in the cabinets, so as to prevent cable dam age due to m echanical stress. Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
Page 22
2, then lead the external battery cables (+, N , -) and a PE cable into the cabinet through guard ring 3. Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
Page 23
3. The battery term inals m ust be conneted firm ly. 4. You can operate batteyr term inals connection only before the U PS pow er-on. Figure 3-3 Connecting battery internal term inals Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
Page 24
1. M enu keys 2. LCD 3. Run indicator 4. A larm indicator 5. Pow er button Figure 4-1 O peration and display panel Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
Page 25
W hen the U PS is started up it perform s a system self-test, during which the Start-up Screen is displayed for approxim ately 10 seconds, as show n in F igure 4-4. Figure 4-4 Start-up screen Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
Page 26
50.00 50.00 50.00 L-L voltage(V) 381.2 381.9 381.7 Input Bypass Battery Output L-N voltage(V) 219.8 220.4 220.4 L-N current(A) 36.0 36.4 36.0 Frequency(Hz) 49.97 49.97 49.97 L-L voltage(V) 381.2 381.7 381.2 Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
Page 27
The Log page can be used to access a list of current and historical UPS events. See below : A b o u t p ag e The About page contains inform ation about the Product, Run tim e, and Eff iciency. See below : Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
Page 28
This prom pt appears w hen you select a com m and of battery restore, Battery reset? O K or Cancel confirm or cancel it Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
Page 29
A bnorm al Inverter The output voltage and bypass voltage are m isaligned in phase. This alarm resets A synchronous autom atically once the condition is no longer true Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
Page 30
A transfer to bypass occurred due to a large step load. The U PS can recover autom atically. Transfer Turn on the load equipm ent in stages to reduce the load im pact on the inverter Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
Page 31
Calibrated Battery The user initiates a battery capacity test (100% capacity discharge) Test M anual Battery The user initiates a m aintenance test (20% capacity discharge) Test Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
Page 32
2 . If the alarm is generated as the result of a softw are value set-up by Vertiv engineer, and you w ish to m odify the setting, please get in touch w ith your local Vertiv custom er service center...
Page 33
The user m ay only sw itch the U PS on once the U PS has been installed com pletely and the authorized service engineer has com pleted the com m issioning tests and shut dow n the external pow er input sw itches. Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
Page 34
Confirm 218.2V 8.2V 充电 50.0Hz Turn on local INV? 563.8V 220.0V 49.9Hz 200.0分 Figure 5-4 Sw itching the U PS on Figure 5-5 Flow page appears after inverter on Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
Select 'YES' to transfer the UPS to Bypass m ode, see F igure 5-7 for the pow er flow page. Confirm 218.0V 220.4V 50.0Hz 充电 50.0Hz Turn off local INV? 553.9V 220.0V 50.0Hz 11.0分 Figure 5-6 Bypass norm al interface Figure 5-7 Flow page on bypass Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
2. The parts of U PS circuits also have hazardous voltage, though the rectifier input sw itch, bypass input sw itch and battery sw itch are disconnected. Therefore, the U PS m aintenance is applicable to qualified personnel only. Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
3. Wait until the test com pletes. After f ive seconds, a pop w indow will appear to show the result of this diagnosis: rectif ier, inverter, m onitor O K or fault. Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
Bypass m ode to N orm al m ode, and the run indicator (green) will be solid on. N ow the U PS restore is com plete. Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
Page 39
LCD inform ation w ill be the displayed in your selected language. See F igure 5-15. Figure 5-15 Changing Language 5. Press the key several tim es to back to the m ain m enu screen. Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
2 . Press the key, the interface show n in F igure 5-21 will appear. Monitor System Input UPS address Card slot protocol YDN23 Password for settings Change settings password 0***** Figure 5-21 Inputting passw ord Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
Page 41
N o te In order to access the U PS param eters, it is necessary to enter the correct passw ord (default: 111111). Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
To achieve coordinated operation of the m odules in the parallel system , it is required to configure each m odule separately using Vertiv setting softw are. This m ust be done by Vertiv service personnel. 6.3.2 C abinet Installation Place the U PS m odules side by side and interconnect as show n in Figure 6-1.
U PS is correct and consistent, that the connection of the parallel cable is reliable, and that the user load is not connected during pow er-on. 4. M easure the m ains voltage and frequency, and verify that they are correct. Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
Before perform ing this procedure, you should check the LCD inform ation first, and m ake sure the bypass is norm al and inverter synchronized. O therw ise, it m ay result in the load pow er interruption for a w hile. Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
Im p o rta n t These procedures shall only be carried out by service personnel of Vertiv or under their guidance. The following procedures are used to reintegrate a U PS m odule that has been previously isolated from the parallel system : 1.
Page 46
In a dual-bus system , the tw o U PS system s m ust have the sam e pow er rating, voltage and frequency, and the load should not exceed the pow er rating of a U PS m odule system . Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
Page 47
(STS), sever power m anagem ent system (SPM ), and so on) produced by Vertiv have netw ork com m unication capability. For m ore inform ation of the SIC card, refer to Site Interface W eb/SN M P Agent C ard U ser M anual.
Page 48
6. The path of m ain m enu screen -> setting -> m onitor ->U PS address is used to set the com m unication address of this U PS through the YD N 23 protocol. Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
Page 49
/Rem ote EPO / M ain input abnorm al / O n J14-1/3 O n_Battery_ REPO port M aintenance Bypass / Load Shed Signal 1 / Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
Page 50
2. If the REPO has been configured to trip an electronically controlled circuit breaker sw itch, after the REPO has been activated it w ill be necessary to re-arm the sw itch before restarting the U PS. Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
Page 51
Charge the battery for at least 12 hours, if the battery hasn't been charged for three m onths at specif ied am bient tem perature, or tw o m onths at high am bient tem perature Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
Page 52
2 . Press the ESC key and check again that the indicators are on, the LCD display is norm al, and that the UPS has been transferred to inverter m ode. Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
Page 53
15 k W 12 k W 9 k W 6 k W 3 k W EXS0030kIBS05 (3 strings of 7A h, 32-block) 30kVA EXS0030kIBS10 strings 9A h, 32-block) Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
Page 54
Internal battery tem perature 0040Kbds01 sensor External W ith LCD screen, connects the SIC card or the m ultifunction port battery tem perature IRM -S01T hum idity sensor Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
Page 55
Refer to Table 9-10 for the com m unication cable’s def inition betw een the U PS and BCB. 外接电池组 BCB BOX 3 2 1 X101 C3板 A8板 1 2 3 4 1 2 3 4 电池输入端子 通信盒 Figure 9-2 Connection of BCB box Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
Page 56
-40°C ~ +70°C (battery excluded), -20°C ~ +30°C (battery included) tem perature for U PS O ver-voltage level O vervoltage level 2 Pollution level Pollution level 2 Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
Page 57
Frequency 50/60 Bypass voltage Settable: +10% , +15% or +20% ; default: +15% % Vac tolerance Settable: -10% , -20% , -30% or -40% ; default: -20% Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
Page 58
-5% , -10% , -15% Low er Lim it In ECO M ode Shared battery Enable, D isable D isable Battery Battery strings 80 ~ 360 Cells per string Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
Page 59
Battery m aintenance test Stop battery test Clear faults Battery capacity test Start equalize charge Stop equalize charge Battery reset M aintain Start m aintenance guide Exit m aintenance guide Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
Page 60
A bout battery: G enerally follow the environm ental protection use period of the battery, otherw ise five years. A pplicable scope: Liebert® EXS 30kVA A nd 40kVA U PS Liebert EXS 30kVA A nd 40kV A U PS U ser M anual...
Need help?