6.3 Procedures for Transfer Between Operation Modes

6.3.1 Transfer from Normal Mode to Battery Mode

Open the external power switch to isolate the mains power and initiate the UPS on battery mode. To transfer the UPS back to
normal mode, close the external power switch to re-connect the mains power to the UPS. 10 seconds later, the rectifier
restarts automatically, and the UPS works in normal mode.

6.3.2 Transfer from Normal Mode to Bypass Mode

Click the Off key as shown in Figure 6.8 below, and the UPS will transfer to bypass mode.
Figure 6.8 Transfer U PS to Bypass m ode
N O TE: In bypass m ode, the load is directly fed by the m ains pow er instead of the pure A C pow er
from the inverter.

6.3.3 Transfer from Bypass Mode to Normal Mode

When the UPS is in bypass mode, click the On key as shown in Figure 6.9 on the next page, and the inverter starts up. Then
the UPS is transferred from bypass mode to normal mode.
6 Single UPS Operation Introduction