Procedures For Transfer Between Operation Modes; Transfer From Normal Mode To Battery Mode; Transfer From Normal Mode To Bypass Mode; Transfer From Bypass Mode To Normal Mode - Vertiv Liebert APM Plus 0500kMK16FN02000 User Manual

50-500 kva ups
Hide thumbs Also See for Liebert APM Plus 0500kMK16FN02000:
Table of Contents

Advertisement

Vertiv™ Liebert® APM Plus User Manual

6.3 Procedures for Transfer Between Operation Modes

6.3.1 Transfer from Normal Mode to Battery Mode

Open the external power switch to isolate the mains power and initiate the UPS on battery mode. To transfer the UPS back to
normal mode, close the external power switch to re-connect the mains power to the UPS. 10 seconds later, the rectifier
restarts automatically, and the UPS works in normal mode.

6.3.2 Transfer from Normal Mode to Bypass Mode

Click the Off key as shown in Figure 6.8 below, and the UPS will transfer to bypass mode.
Figure 6.8 Transfer UPS to Bypass mode
NOTE: In bypass mode, the load is directly fed by the mains power instead of the pure AC power from the inverter.

6.3.3 Transfer from Bypass Mode to Normal Mode

When the UPS is in bypass mode, click the On key as shown in Figure 6.9 on the facing page, and the inverter starts up. Then
the UPS is transferred from bypass mode to normal mode.
116
Proprietary and Confidential ©2023 Vertiv Group Corp.